Skip to main content
Siemens 4EU2521-5DA00-0A — Line/Load Reactors

Siemens 4EU2521-5DA00-0A Commutating Choke, 175A 3-Phase

MPN4EU2521-5DA00-0A

Siemens 4EU2521-5DA00-0A commutating choke (line reactor) for converter drives, 3-phase, 380V AC, 175A max / 158A rated, 0.16 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2521-5DA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.00016H
Relative inductive voltage drop4%
4EU2521-5DA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2521-5DA00-0A — Electrical
ParameterValue
Rated operating voltage380V
Number of phases3
Rated current (DC)214.4A
Voltage typeAC
Rated operating frequency0 ... 50Hz
4EU2521-5DA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)105W
Power loss, iron core (W)70W
Rated ambient temperature40°C
4EU2521-5DA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2521-5DA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

The Siemens 4EU2521-5DA00-0A is a commutating choke for converter drives — a 3-phase line reactor rated 380 V AC with a maximum continuous current of 175 A and a rated current of 158 A. This is the current-limiting element that sits between the AC supply and a variable-frequency drive or DC drive input — without it, the converter's switching transients can weld contactors and blow upstream fuses. The 175 A maximum governs the upstream MCCB or fuse sizing, not the motor full-load amps; the choke's own thermal capacity sets the floor.

Three-phase, 380 V AC, 50 Hz. The 0–50 Hz operating frequency range means it is designed for standard line frequency — not for the variable output of a VFD. At DC, the rated value is 214.4 A — this matters if the choke is used on the DC link of a drive, but the primary application is AC line side. Thermal class H per IEC 60085 means the insulation system withstands 180 °C hot-spot temperature — standard for converter-duty reactors that see harmonic heating. The total power loss splits between the coil (105 W) and the iron core (70 W); plan for 175 W of heat rejection inside the enclosure. IP00 means no ingress protection — this is an open-frame component for a clean, dry cabinet, not for outdoor or washdown duty.

Integration and deployment

Mounting dimensions: 0.225 m wide, 0.21 m tall, 0.16 m deep. This is a panel-mount component — no DIN rail clip. The flat-type terminals accept busbar or cable lug connections; plan for 0.2–0.5 m of clearance above and below for airflow and lug access. In a 380 V drive cabinet, this choke typically mounts between the input circuit breaker and the drive input terminals.

Frequently asked questions

What are the key ratings of the 4EU2521-5DA00-0A commutating choke?

Three-phase, 380 V AC, 50 Hz, 175 A maximum continuous current, 158 A rated current, 0.16 mH inductance, 4% voltage drop, IP00 enclosure, thermal class H insulation.

Where can I buy the 4EU2521-5DA00-0A?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
4EU2521-5DA00-0A