Skip to main content
Siemens 4EU2522-0CA00-0AA0 — Line/Load Reactors

4EU2522-0CA00-0AA0 Commutating Choke, 126A, 0.2mH, IP00

MPN4EU2522-0CA00-0AA0

Siemens 4EU2522-0CA00-0AA0, commutating choke for converter, 3-phase, 500V AC, 126A rated current, 0.2mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2522-0CA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0002H
Relative inductive voltage drop4%
4EU2522-0CA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2522-0CA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)171.5A
Voltage typeAC
Rated operating frequency50Hz
Peak current175A
4EU2522-0CA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)135W
Power loss, iron core (W)52W
Rated ambient temperature40°C
4EU2522-0CA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2522-0CA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

The Siemens 4EU2522-0CA00-0AA0 is a three-phase commutating choke (line reactor) designed for the DC link of a converter drive. Its job is to limit the rate of rise of current (di/dt) during thyristor or IGBT commutation, reducing harmonic distortion and protecting the converter's semiconductor switches. The 0.2 mH inductance and 4% relative inductive voltage drop are sized for a 500 V AC, 50 Hz supply, carrying a rated continuous current of 126 A and a maximum of 140 A, with a peak current capability of 175 A.

The 126 A rated current (I LN) is the continuous thermal current at the rated ambient of 40 °C. The 140 A maximum (I thmax) is the thermal limit for overload conditions at 50 Hz. The 175 A peak current is the non-repetitive surge rating — important for sizing upstream fuses or a circuit breaker that must pass the inrush without nuisance tripping. Total power loss is 187 W (135 W in the coil plus 52 W in the iron core), which must be dissipated within the enclosure; the IP00 rating means this choke is not protected against dust or moisture ingress and requires installation inside a cabinet with at least IP2X or better. Thermal class H insulation (180 °C hot-spot) gives margin for high-ambient or overloaded installations.

Mounting and connection

The choke measures 0.225 m wide by 0.21 m high by 0.16 m deep. Main circuit connections are via flat-type terminals, typical for bolted bus-bar or cable-lug terminations in a drive cabinet. The IP00 chassis-mount design means it must be bolted to a grounded metal panel inside the enclosure; no DIN-rail clip is provided. Verify the available panel footprint against the 225 mm width and 160 mm depth before committing the layout.

Frequently asked questions

What are the key specifications of this commutating choke?

Rated current 126 A, maximum current 140 A, peak current 175 A, inductance 0.2 mH, operating voltage 500 V AC, frequency 50 Hz, IP00, thermal class H, flat-type terminals.

Where can I buy 4EU2522-0CA00-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time.

MPN
4EU2522-0CA00-0AA0