It's rated for 400 V AC at 50/60 Hz, with a maximum AC current of 164 A and a continuous rated operational current of 147.6 A. The 0.18 mH inductance and 4% relative inductive voltage drop tell you the impedance it adds to the circuit, which is what smooths the current waveform and protects the converter's input stage. Open-frame IP00 component for panel installation. Flat-type terminals accept busbar or cable lugs. Thermal class H insulation.
Maximum AC current 164 A at 60 Hz. Rated operational current 147.6 A at 400 V, 50 Hz, 50 °C ambient. DC rated current 200.9 A. Coil loss 123 W, iron-core loss 92.9 W. Width 0.225 m, height 0.21 m, depth 0.16 m.