Skip to main content
Siemens 4EU2522-3BA00-0AA0 — Line/Load Reactors

Siemens 4EU2522-3BA00-0AA0 Commutating Choke, 160 A, 400 V,

MPN4EU2522-3BA00-0AA0
Active

Siemens 4EU2522-3BA00-0AA0, commutating choke for converter, 3-phase, 400 V AC, 50 Hz, 160 A max AC, 0.13 mH, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU2522-3BA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00013H
Relative inductive voltage drop4%
4EU2522-3BA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2522-3BA00-0AA0 — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)144A
Number of phases3
Current (AC), max.160A
Rated current (DC)196A
Voltage typeAC
Rated operating frequency50Hz
4EU2522-3BA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)135W
Power loss, iron core (W)52W
Rated ambient temperature40°C
4EU2522-3BA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2522-3BA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

What this choke does in a drive line

The Siemens 4EU2522-3BA00-0AA0 is a 3-phase commutating choke (also called a line reactor) sized for converter input circuits. It limits current rise and harmonics on the AC side of a variable-frequency drive or DC drive supply.

Three current figures govern selection here. The 160 A AC maximum is the thermal limit under worst-case conditions — the choke can sustain that continuously without exceeding its 135 W coil loss and 52 W iron loss at 40 °C ambient. The 144 A AC operational current is the continuous rating under rated voltage and frequency; that is the number to match against your drive's input current at full load. For DC-side applications, the 196 A DC rated value applies — useful if the choke is placed in the DC link rather than the AC line. Thermal class H insulation (180 °C hot-spot) gives headroom for overloads and high ambient temperatures inside a sealed cabinet.

Mounting and connection

IP00 means no enclosure — this choke is intended for mounting inside a panel or drive cubicle where it is protected from dust and contact. The main circuit connects via flat-type terminals (bus-bar style), not screw clamps or spring cages. Physical footprint is 0.225 m wide by 0.21 m tall by 0.16 m deep. Plan for bus-bar routing and adequate clearance around the terminals for torque tools.

Listed as active in the manufacturer's lifecycle system.

Frequently asked questions

What is the physical size of 4EU2522-3BA00-0AA0?

Width 0.225 m, height 0.21 m, depth 0.16 m. Flat-type terminals for bus-bar connection.