Skip to main content
Siemens 4EU2532-0CE08-4BA0 — Line/Load Reactors

SIDAC 4EU2532-0CE08-4BA0 Filter Reactor, 3-Phase, 40.6A, 460

MPN4EU2532-0CE08-4BA0

SIDAC 4EU2532-0CE08-4BA0, 3-phase filter reactor, 40.6A rated, 460V AC, 60Hz, 7% throttling factor, 30 kvar, IP00, free cable endings.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2532-0CE08-4BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0014H
Relative throttling factor7%
Filter resonant frequency189Hz
Rated reactive power (filter bank)30 000var
4EU2532-0CE08-4BA0 — Identification
ParameterValue
Product designationfilter reactor
4EU2532-0CE08-4BA0 — Electrical
ParameterValue
Rated operating voltage460V
Number of phases3
Voltage typeAC
Rated operating frequency60Hz
4EU2532-0CE08-4BA0 — Losses & Thermal
ParameterValue
Total power loss (W)162.1W
Rated ambient temperature55°C
4EU2532-0CE08-4BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2532-0CE08-4BA0 — Mechanical
ParameterValue
Main-circuit connection typefree cable endings
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

The SIDAC 4EU2532-0CE08-4BA0 is a 3-phase filter reactor rated for 40.6A continuous at 460V AC, 60Hz. The 7% relative throttling factor means it drops roughly 7% of line voltage at rated current — standard for drives input reactors that limit harmonic distortion and reduce peak currents on the DC bus. The 30 kvar reactive power rating confirms it's sized for a VFD bank or a harmonic filter bank in that power class.

Rated 40.6A with a 45.1A maximum — the continuous duty point for a 3-phase load. That 45.1A ceiling is the thermal limit; a drive drawing 45A sustained will push the winding temperature past the Class H (180°C) insulation rating at 55°C ambient. IP00 means no ingress protection — this reactor lives inside a cabinet, not on the plant floor. Free cable endings on the main circuit mean you terminate directly; no terminal block, so plan for a junction box or lug kit in the panel layout.

Footprint is 0.225m wide by 0.21m tall, 0.16m deep — a compact block for a 30 kvar reactor. Mounts inside a standard 600mm-wide enclosure with room for the free cable bends. Thermal class H insulation means it can sit near other heat sources in the cabinet, but the 162.1W dissipation still needs airflow. The 189Hz resonant frequency is the self-resonance of the winding — keep the drive carrier frequency away from that point to avoid exciting the core.

Frequently asked questions

Where can I buy 4EU2532-0CE08-4BA0 and get current pricing?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ to receive a firm offer.

What does the 7% throttling factor mean for my drive installation?

The 7% relative throttling factor means the reactor drops approximately 7% of the line voltage at rated current (40.6A). This is the standard impedance for drive input reactors used to limit harmonic distortion and reduce DC bus peak currents.

What is the resonant frequency of this filter reactor?

The self-resonant frequency is 189Hz. Avoid operating the drive carrier frequency near this point to prevent core excitation and audible noise.

MPN
4EU2532-0CE08-4BA0