Skip to main content
Siemens 4EU2532-0ME08-0AA0 — Line/Load Reactors

SIDAC 4EU2532-0ME08-0AA0 Filter Reactor, 90.4A, 220V

MPN4EU2532-0ME08-0AA0

SIDAC 4EU2532-0ME08-0AA0, 3-phase filter reactor, 90.4 A rated, 220 V AC, 50 Hz, 5.67 % throttling factor, IP00, screw/flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2532-0ME08-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00031H
Relative throttling factor5.67%
Filter resonant frequency210Hz
Rated reactive power (filter bank)30 000var
4EU2532-0ME08-0AA0 — Identification
ParameterValue
Product designationfilter reactor
4EU2532-0ME08-0AA0 — Electrical
ParameterValue
Rated operating voltage220V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2532-0ME08-0AA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU2532-0ME08-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2532-0ME08-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

Filter Reactor for Harmonic Mitigation

The SIDAC 4EU2532-0ME08-0AA0 is a 3-phase filter reactor rated for 90.4 A continuous at 220 V AC, 50 Hz. With a relative throttling factor of 5.67% and a resonant frequency of 210 Hz, it is sized to suppress the 5th harmonic (250 Hz) and adjacent ripple from 6-pulse rectifier drives — the dominant source of line-side harmonics in industrial VFD banks. The 30 kvar reactive power rating means it can support a capacitor bank of that size without saturating the core.

IP00 means it is an open-frame component — no enclosure, no drip shield. It must be installed inside a cabinet with at least IP2X protection, and the 0.21 m height, 0.225 m width, and 0.16 m depth footprint (roughly 225 × 210 × 160 mm) need clearance around the core for natural convection cooling. The thermal class H (180 °C insulation system) allows a 40 °C ambient without derating, but above that you follow the IEC 60085 temperature-rise limits. Terminals are flat connector / screw-type — expect bus-bar or ring-tongue lugs on the main circuit. The 100 A maximum rating gives headroom above the 90.4 A continuous; this is typical for a reactor that must handle transient overloads without saturating.

Frequently asked questions

Where can I buy 4EU2532-0ME08-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What does the 5.67% throttling factor mean for harmonic filtering?

The 5.67% relative throttling factor, combined with a 210 Hz resonant frequency, means this reactor is tuned to attenuate the 5th harmonic (250 Hz) from 6-pulse rectifiers. It provides a typical impedance of 5.67% at the fundamental 50 Hz, which limits harmonic current injection into the supply.

Can I use 4EU2532-0ME08-0AA0 outdoors?

No — the IP00 protection class means no ingress protection against dust or moisture. It requires installation inside an enclosure rated for the environment (e.g., IP54 or higher for outdoor use).

MPN