Siemens 4EU2532-0MG08-0AA0 — Line/Load Reactors

SIDAC 4EU2532-0MG08-0AA0 Filter Reactor, 49.2A, 480V, 3-Phas

MPN4EU2532-0MG08-0AA0

SIDAC 4EU2532-0MG08-0AA0, 3-phase filter reactor, 49.2 A rated / 54.6 A max, 480 V AC, 60 Hz, 40 kvar, 1.2 mH, 7 % throttling, IP00, screw/flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2532-0MG08-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0012H
Relative throttling factor7%
Filter resonant frequency227Hz
Rated reactive power (filter bank)40 000var
4EU2532-0MG08-0AA0 — Identification
ParameterValue
Product designationfilter reactor
4EU2532-0MG08-0AA0 — Electrical
ParameterValue
Rated operating voltage480V
Number of phases3
Voltage typeAC
Rated operating frequency60Hz
4EU2532-0MG08-0AA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU2532-0MG08-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2532-0MG08-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

What this reactor does in the line

The SIDAC 4EU2532-0MG08-0AA0 is a 3-phase filter reactor rated for 49.2 A continuous with a 54.6 A maximum, at 480 V AC, 60 Hz. It delivers 40 kvar of reactive power and 1.2 mH inductance with a 7% relative throttling factor — meaning it's sized to limit harmonic current and voltage notching for a drive or UPS input, not just smooth DC ripple. The 227 Hz resonant frequency places the trap below the 5th harmonic (300 Hz at 60 Hz fundamental), so it knocks down the 5th and 7th harmonics that cause the most motor heating and capacitor stress. Thermal class H (180 °C) insulation gives headroom for continuous full-load operation at 40 °C ambient without derating.

Physical fit and terminals

Footprint is 0.225 m wide by 0.21 m tall, 0.16 m deep — it's a panel-mount block, not DIN-rail. IP00 means no enclosure; it's intended for a ventilated cabinet where the reactor's own heat (class H) can convect away. Main circuit connections are flat connector / screw-type terminals, so you'll need bus bars or ring-lug cable lugs sized for the 49.2 A continuous path.

Frequently asked questions

Where can I buy 4EU2532-0MG08-0AA0 and how is it quoted?

This part is sourced through independent distribution channels. Submit an RFQ for current pricing and availability — we confirm both at quote time, no stock figures on the public page.

What is the 4EU2532-0MG08-0AA0's key rating for sizing?

The continuous rated current is 49.2 A with a 54.6 A maximum, at 480 V AC, 60 Hz, 3-phase. The reactive power rating is 40 kvar. That's the number to match against your drive or filter bank input.

MPN
4EU2532-0MG08-0AA0