Siemens 4EU2552-0AE00-0A — Line/Load Reactors

Siemens 4EU2552-0AE00-0A Mains Choke, 36 A, 600 V, 1 mH

MPN4EU2552-0AE00-0A

Siemens 4EU2552-0AE00-0A mains choke (Netzdrossel), 36 A, 600 V AC, 1 mH, 20 Hz, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2552-0AE00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.001H
Relative inductive voltage drop1.3%
4EU2552-0AE00-0A — Identification
ParameterValue
Product designationNetzdrossel
4EU2552-0AE00-0A — Electrical
ParameterValue
Rated operating voltage600V
Number of phases3
Voltage typeAC
Rated operating frequency20Hz
4EU2552-0AE00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)123W
Power loss, iron core (W)98.5W
Rated ambient temperature55°C
4EU2552-0AE00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2552-0AE00-0A — Mechanical
ParameterValue
Main-circuit connection typefree cable endings
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.16m

Product details

The Siemens 4EU2552-0AE00-0A is a three-phase mains choke (Netzdrossel) — a line reactor sized for 36 A maximum continuous current, 32.4 A rated current, at 600 V AC, 20 Hz operating frequency. Its 1 mH inductance limits harmonic distortion and inrush current on the line side of a drive or power supply. Rated inductance of 0.001 H (1 mH) with a relative inductive voltage drop of 1.3 % at the measurement level — a typical figure for a line reactor that smooths current without excessive voltage sag under load.

Thermal and enclosure reality

IP00 means no enclosure protection — the choke is an open-frame component intended for mounting inside a cabinet or panel that provides the IP rating. Free cable endings for the main circuit connection, so you terminate directly into your power wiring. Thermal class H per IEC 60085 allows a 180 °C hot-spot temperature, which is standard for high-temp reactor windings. The coil dissipates 123 W and the iron core 98.5 W — total 221.5 W of heat that must be removed by cabinet ventilation or derating at elevated ambient temperatures. Rated ambient temperature is 55 °C; above that, you derate current per the manufacturer's thermal curve (not reproduced here). The 0.225 m width, 0.21 m height, and 0.16 m depth give a compact footprint for a 36 A three-phase reactor.