Skip to main content
Siemens 4EU2552-3UB00-0AA0 — Line/Load Reactors

Siemens 4EU2552-3UB00-0AA0 Mains Choke, 90A, 0.37mH, 3-Phase

MPN4EU2552-3UB00-0AA0

Siemens 4EU2552-3UB00-0AA0 mains choke (Netzdrossel f. FU), 3-phase, 500V AC, 90A rated current, 0.37mH inductance, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2552-3UB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00037H
Relative inductive voltage drop4%
4EU2552-3UB00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2552-3UB00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2552-3UB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)139W
Power loss, iron core (W)44W
Rated ambient temperature40°C
4EU2552-3UB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2552-3UB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.176m

Product details

Mains Choke for Variable Frequency Drives

The Siemens 4EU2552-3UB00-0AA0 is a three-phase mains choke (line reactor) designed for use with variable frequency drives. It carries a rated current of 90 A and a maximum current of 100 A, with an inductance of 0.37 mH and a 4% relative inductive voltage drop at rated conditions. This choke sits between the supply and the drive input to reduce harmonic distortion, limit inrush current, and protect the drive's DC bus from line transients.

The 0.37 mH inductance and 4% impedance at rated current are matched to a typical drive input stage — this isn't a random value; it's sized to keep harmonic currents below IEEE 519 thresholds for most 90–100 A drive installations. The 139 W coil loss and 44 W core loss total 183 W heat dissipation at full load — factor that into enclosure ventilation. Thermal class H insulation, 40 °C ambient rating. IP00 enclosure, open-frame. Flat-type terminals for main circuit.

Designed to EN 61558-2-20 and carries UL/CSA recognition per the manufacturer's marking. The UL/CSA mark means it's accepted in North American panels without a separate component evaluation — a practical gate for export builds or multi-site BOMs.

Frequently asked questions

What compliance documentation does Siemens provide for this choke?

The part is designed to EN 61558-2-20 and carries UL/CSA recognition as marked on the nameplate. UL/CSA acceptance covers North American panel installations.

MPN