Skip to main content
Siemens 4EU2552-7UA00-0AA0 — Line/Load Reactors

Siemens 4EU2552-7UA00-0AA0 Mains Choke, 90A, 690V, 0.25 mH

MPN4EU2552-7UA00-0AA0

Siemens 4EU2552-7UA00-0AA0 mains choke (line reactor) for frequency converters, 3-phase, 690V AC, 90A rated / 100A max, 0.25 mH, IP00, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2552-7UA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00025H
Relative inductive voltage drop2%
4EU2552-7UA00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2552-7UA00-0AA0 — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2552-7UA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)140W
Power loss, iron core (W)43W
Rated ambient temperature40°C
4EU2552-7UA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2552-7UA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.176m

Product details

What this choke does in the drive line

The Siemens 4EU2552-7UA00-0AA0 is a 3-phase mains choke (line reactor) sized for variable-frequency drive input circuits.

Thermal class and power dissipation

Total power loss splits between the coil (140 W) and the iron core (43 W), for 183 W dissipated at rated load. Thermal class H per IEC 60085 means the insulation system handles a 180 °C hot-spot temperature — relevant if this choke sits in a crowded cabinet where ambient already runs 40 °C. The open-frame IP00 construction means it needs enclosure-level protection; it is not a standalone device for a wet or dusty floor.

Termination and approvals

Main circuit connection uses flat-type terminals — expect bus-bar or crimp-lug termination, not a spring cage. The choke carries UL/CSA recognition per EN 61558-2-20, which covers transformers and reactors for industrial applications. That recognition matters for panel builders who need a cUL-marked component to pass a North American inspection.

MPN
4EU2552-7UA00-0AA0