Skip to main content
Siemens 4EU2722-0DA00-1BA0 — Line/Load Reactors

Siemens 4EU2722-0DA00-1BA0 Commutating Choke, 180A, 690V, IP

MPN4EU2722-0DA00-1BA0

Siemens 4EU2722-0DA00-1BA0, commutating choke for converter, 3-phase, 180 A rated, 690 V AC, 0.19 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-0DA00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00019H
Relative inductive voltage drop4%
4EU2722-0DA00-1BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-0DA00-1BA0 — Electrical
ParameterValue
Rated operating voltage0, 690V
Number of phases3
Rated current (DC)245A
Voltage typeAC
Rated operating frequency0 ... 50Hz
Peak current250A
4EU2722-0DA00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)190W
Power loss, iron core (W)90W
Rated ambient temperature40°C
4EU2722-0DA00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-0DA00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-0DA00-1BA0 is a 3-phase commutating choke for converter applications, rated at 180 A continuous with a peak current capacity of 250 A. It handles AC voltages up to 690 V and provides an inductance of 0.19 mH, with a relative inductive voltage drop of 4% at rated current. The choke is designed for line-side or load-side use in variable-speed drive systems, limiting current rise during commutation and reducing harmonic distortion on the supply.

Key ratings and their meaning

Rated 180 A continuous, 200 A maximum. 250 A peak handles short-duration overloads. 4% voltage drop at rated current. Thermal class H (180 °C) insulation. Coil loss 190 W, iron core loss 90 W. IP00 means no enclosure — the choke is a bare magnetic assembly with flat-type terminals. The flat connectors accept busbar or cable lugs; plan for proper creepage and clearance distances per IEC 61558-2-20, which is the standard cited in the full description.

Panel-mount component. Width 0.27 m, height 0.248 m, depth 0.187 m. Flat-type terminals for main circuit. Designed for a 3-phase AC supply at 50 Hz or below (0 to 50 Hz operating frequency), it is a line-frequency choke, not a high-frequency output filter. Use it on the line side of a 6-pulse or 12-pulse rectifier, or on the DC link if the circuit is configured for that.

Frequently asked questions

What is the physical size of 4EU2722-0DA00-1BA0?

Width 0.27 m, height 0.248 m, depth 0.187 m. It is a panel-mount component with flat-type terminals for the main circuit.

MPN
4EU2722-0DA00-1BA0