Siemens 4EU2722-0FA00-1BA0 Commutating Choke, 246A, 400V AC

MPN4EU2722-0FA00-1BA0

Siemens 4EU2722-0FA00-1BA0 commutating choke for converter, 3-phase, AC, 400V, 246A max, 0.12 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU2722-0FA00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00012H
Relative inductive voltage drop4%
4EU2722-0FA00-1BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-0FA00-1BA0 — Electrical
ParameterValue
Rated operating voltage400, 400V
Rated current (AC)221.4A
Number of phases3
Current (AC), max.246A
Rated current (DC)301.4A
Voltage typeAC
Rated operating frequency60 ... 50Hz
4EU2722-0FA00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)160W
Power loss, iron core (W)127W
Rated ambient temperature50°C
4EU2722-0FA00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-0FA00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-0FA00-1BA0 is a 3-phase commutating choke for converter applications, rated for 400 V AC at 50/60 Hz. It handles a maximum AC current of 246 A and a rated operational current of 221.4 A, with an inductance of 0.12 mH. The relative inductive voltage drop is 4% at rated current, voltage, and frequency.

The 0.12 mH inductance and 4% voltage drop define the commutation notch filtering — this choke is sized to limit di/dt and suppress harmonics for a specific converter DC-link current. The 301.4 A DC rated value tells you the choke can also sit in the DC link path, not just the AC input.

Deployment Context

IP00 means no ingress protection — this choke is for installation inside a cabinet or enclosure, not in a washdown or outdoor location. The flat-type terminals accept busbar or crimp lugs, not standard wire ferrules. Thermal class H per IEC 60085 means the insulation system can sustain 180 °C hot-spot temperature, which is typical for high-power converter chokes running at 160 W coil loss plus 127 W iron-core loss at 50 °C ambient. Mount it with clearance for airflow; forced ventilation is advisable above 246 A continuous.

Frequently asked questions

Where can I buy 4EU2722-0FA00-1BA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What are the key electrical ratings for 4EU2722-0FA00-1BA0?

It is a 3-phase AC commutating choke rated 400 V, 50/60 Hz, with a maximum AC current of 246 A, a rated operational current of 221.4 A, and a DC rated current of 301.4 A. Inductance is 0.12 mH with a 4% relative inductive voltage drop.

What is the IP rating and thermal class?

Protection class is IP00 — no ingress protection, for cabinet installation only. Thermal class is H per IEC 60085, rated for 180 °C hot-spot temperature.

MPN