The 0.075mH inductance and 2% relative inductive voltage drop define its harmonic filtering and inrush current limiting behavior — the 2% drop is the figure that governs how much voltage sag the drive sees under load, so it's the one to match against your drive's DC bus tolerance.
Open-frame IP00 construction means it's intended for enclosure mounting — no touch protection on the terminals, so it goes inside a locked panel or cabinet. Dimensions are 0.27m wide by 0.248m tall by 0.208m deep. The main circuit connects via flat-type terminals, which typically require a busbar or crimp lug — not a standard ring terminal. Plan for 130W coil losses plus 55W iron-core losses as heat to vent; at 185W total dissipation, it needs forced airflow or generous natural convection in the enclosure.
Thermal and insulation class
Rated for 40°C ambient with Class H insulation per IEC 60085. Class H means the winding can handle 180°C hot-spot temperature — that's the safety margin if your panel runs hot or the choke is near other heat sources. The 40°C ambient rating is the reference point; above that, derate per the manufacturer's curve (not provided here, but standard for Class H).