Siemens 4EU2722-0FG00-0BA0 — Line/Load Reactors

Siemens 4EU2722-0FG00-0BA0 Mains Choke, 3-Phase, 500V, 200A,

MPN4EU2722-0FG00-0BA0

Siemens 4EU2722-0FG00-0BA0 mains choke for frequency converters, 3-phase AC, 500V rated voltage, 200A max current, 75 µH, 2% voltage drop, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU2722-0FG00-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000075H
Relative inductive voltage drop2%
4EU2722-0FG00-0BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2722-0FG00-0BA0 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)180A
Number of phases3
Current (AC), max.200A
Voltage typeAC
Rated operating frequency60Hz
4EU2722-0FG00-0BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)143W
Power loss, iron core (W)46W
Rated ambient temperature40°C
4EU2722-0FG00-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-0FG00-0BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.208m

Product details

What this choke does in a drive cabinet

The Siemens 4EU2722-0FG00-0BA0 is a 3-phase mains choke (Netzdrossel f. FU) sized for frequency converter input lines. Its 200 A maximum AC current and 180 A rated operational current at 500 V AC, 60 Hz, with 75 µH inductance and a 2% relative inductive voltage drop, mean it smooths line-side harmonics and limits inrush current for drives in that current class. The IP00 enclosure (no protection against dust or moisture) tells you this mounts inside a panel or cabinet — not on the machine frame where washdown or dust exposure is a risk. Thermal class H insulation (IEC 60085) handles the 143 W coil losses plus 46 W iron core losses at 40 °C ambient, so it runs hot but stays within rating in a ventilated enclosure.

Physical fit and connection

Dimensions: 0.208 m depth, 0.27 m width, 0.248 m height. The main current circuit terminates on flat-type connectors — expect busbar or compression-lug terminations, not screw-clamp or spring-cage. Panel builders should verify the flat-connector pitch and hole pattern against their existing busbar layout before committing the footprint.

Frequently asked questions

Where can I buy the 4EU2722-0FG00-0BA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key electrical ratings for the 4EU2722-0FG00-0BA0?

Three-phase AC, 500 V rated voltage, 200 A maximum AC current, 180 A rated operational current at 60 Hz, 75 µH inductance, 2% voltage drop. Coil losses are 143 W and iron core losses 46 W at 40 °C ambient.

What protection class does the 4EU2722-0FG00-0BA0 have?

IP00 — no protection against dust ingress or water. It must be installed inside a panel or cabinet that provides the environmental sealing.