Skip to main content
Siemens 4EU2722-0GC00-1BA0 — Line/Load Reactors

Siemens 4EU2722-0GC00-1BA0 Mains Choke, 150 A, 500 V, 50 Hz

MPN4EU2722-0GC00-1BA0

Siemens SENTRON 4EU2722-0GC00-1BA0 mains choke (Netzdrossel), 3-phase, 150 A max / 135 A rated, 500 V AC, 50 Hz, 0.3 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-0GC00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0003H
Relative inductive voltage drop4.8%
4EU2722-0GC00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel
4EU2722-0GC00-1BA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2722-0GC00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)156W
Power loss, iron core (W)73W
Rated ambient temperature40°C
4EU2722-0GC00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-0GC00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-0GC00-1BA0 is a three-phase mains choke (Netzdrossel) rated for 150 A maximum current and 135 A continuous rated current at 500 V AC, 50 Hz. The 0.3 mH inductance limits harmonic distortion and reduces peak currents on the input side of a variable-frequency drive or rectifier. The 156 W coil loss plus 73 W iron core loss (229 W total at rated conditions) is the heat you need to vent; IP00 means this is an open-frame component for cabinet mounting, not a standalone enclosure.

Where it fits — panel integration and thermal class

This choke measures 0.27 m wide, 0.248 m high, and 0.187 m deep — a compact footprint for a 150 A three-phase reactor. The flat-connector main terminals accept busbar or cable lugs; plan for a bolted connection rather than spring-cage wiring. Thermal class H per IEC 60085 means the insulation system withstands 180 °C hot-spot temperature, so it can sit in a warm cabinet alongside drives without derating — provided ambient stays at or below the 40 °C rating. The IP00 protection class means no dust or splash protection; mount it inside a panel with at least IP54 clearance from live parts.

Frequently asked questions

What are the key electrical ratings for 4EU2722-0GC00-1BA0?

150 A maximum, 135 A rated continuous current, 500 V AC operating voltage, 50 Hz frequency, 0.3 mH inductance, and a 4.8% relative inductive voltage drop at rated conditions.

Where can I buy the 4EU2722-0GC00-1BA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What compliance documentation comes with this mains choke?

The part is listed as compliant with EN 61558-2-20, which covers safety requirements for chokes and reactors. RoHS, REACH, and UL documentation should be available from the manufacturer upon request.

MPN
4EU2722-0GC00-1BA0