Skip to main content
Siemens 4EU2722-3AA00-0AA0 — Line/Load Reactors

Siemens 4EU2722-3AA00-0AA0 Commutating Choke, 250A, 225A Rat

MPN4EU2722-3AA00-0AA0

Siemens 4EU2722-3AA00-0AA0 commutating choke for converter, 3-phase, 400V AC, 50Hz, 250A max / 225A rated, 0.112mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-3AA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00011H
Relative inductive voltage drop4%
4EU2722-3AA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-3AA00-0AA0 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)306.3A
Voltage typeAC
Rated operating frequency50Hz
4EU2722-3AA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)167W
Power loss, iron core (W)90W
Rated ambient temperature40°C
4EU2722-3AA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-3AA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-3AA00-0AA0 is a three-phase commutating choke (line reactor) designed for use with power converters and drives. It limits current rise and reduces harmonic distortion on the line side of a converter, protecting both the drive and the upstream supply. Rated for 400 V AC at 50 Hz, it carries a maximum continuous current of 250 A and a rated current of 225 A, with an inductance of 0.112 mH (110 µH). The 4% relative inductive voltage drop (on the measurement level) means this choke introduces a predictable impedance that helps the converter meet line-side harmonic limits without excessive voltage sag under load. At 225 A continuous, the total power loss splits between the coil (167 W) and the iron core (90 W), so panel ventilation must account for roughly 257 W of heat rejection at full rated current. With an IP00 protection class, this choke has no enclosure — it is an open-frame component intended for installation inside a switchgear cabinet or drive panel. The flat-type main circuit terminals accept busbar or cable lugs; plan for adequate clearance to live parts per local wiring regulations.

Thermal class and ambient rating

Rated for a 40 °C ambient temperature and wound to thermal class H per IEC 60085, meaning the insulation system withstands a continuous hot-spot temperature of 180 °C. This gives headroom for installations where the choke shares a cabinet with heat-producing drives, as long as the ambient air at the choke intake stays at or below 40 °C.

Physical dimensions

The choke measures 0.270 m wide, 0.248 m high, and 0.187 m deep. These dimensions are for the body only — allow additional space for cable bending radius and busbar connections above the flat terminals.

Frequently asked questions

Where can I buy 4EU2722-3AA00-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to receive a firm price and lead time for your required quantity.

What is the inductance and voltage drop of this choke?

The rated inductance is 0.112 mH (110 µH), and the relative inductive voltage drop is 4% at the rated current, voltage, and frequency. This drop is measured at the rated operating point and determines the choke's impedance contribution to the circuit.

MPN
4EU2722-3AA00-0AA0