Siemens 4EU2722-3CA00-0AA0 Commutating Choke, 3-Phase, 500V,

MPN4EU2722-3CA00-0AA0

Siemens 4EU2722-3CA00-0AA0 commutating choke for converter applications, 3-phase AC, 500V, 224A max AC current, 0.13 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-3CA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00013H
Relative inductive voltage drop4%
4EU2722-3CA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-3CA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)201.6A
Number of phases3
Current (AC), max.224A
Rated current (DC)274.5A
Voltage typeAC
Rated operating frequency50Hz
Peak current280A
4EU2722-3CA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)174W
Power loss, iron core (W)80W
Rated ambient temperature40°C
4EU2722-3CA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-3CA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

It handles a maximum AC current of 224 A and a peak current of 280 A, with a rated inductance of 0.13 mH and a relative inductive voltage drop of 4% at rated current. That 4% drop is the key spec for sizing — it tells you the impedance the choke adds to the DC link or line side, which governs how much it limits di/dt and reduces harmonic distortion on the converter input.

This is an open-frame (IP00) choke — no enclosure, so it needs to live inside a panel or cabinet where it's protected from dust and contact. Mounting dimensions are 0.27 m wide by 0.248 m tall by 0.187 m deep. The main circuit connections are flat-type terminals, which means you'll need either flat busbars or ring-tongue cable lugs sized for the 224 A continuous current. Thermal class H insulation (180°C rated) means the coil can run hot without degrading the magnet wire — important when the choke is packed into a cabinet with other heat sources.

Total power loss breaks down to 174 W in the coil and 80 W in the iron core, so you're looking at about 254 W of heat to manage inside the panel. That's not trivial — factor it into your cabinet cooling calculation, especially if the drive and choke share the same enclosure. The DC-rated current is 274.5 A, which is higher than the AC rating; that's typical for a choke where the DC current in the link is the limiting factor for saturation, while the AC rating governs the line-side harmonic performance.

Frequently asked questions

Where can I buy 4EU2722-3CA00-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings for 4EU2722-3CA00-0AA0?

It's a 3-phase commutating choke rated for 500 V AC at 50 Hz, with a maximum AC current of 224 A, peak current of 280 A, and inductance of 0.13 mH. The relative inductive voltage drop is 4% at rated current.

What is the physical size of 4EU2722-3CA00-0AA0?

The dimensions are 0.27 m wide by 0.248 m tall by 0.187 m deep. It's an open-frame IP00 design, so it mounts inside a panel or cabinet.

MPN
4EU2722-3CA00-0AA0