Skip to main content
Siemens 4EU2722-6AA00-0AA0 — Line/Load Reactors

Siemens 4EU2722-6AA00-0AA0 Commutating Choke, 162A, 500V, 3-

MPN4EU2722-6AA00-0AA0

Siemens SENTRON 4EU2722-6AA00-0AA0 commutating choke for converter, 3-phase, 500V AC, 162A rated, 180A max, 0.2 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-6AA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0002H
Relative inductive voltage drop4%
4EU2722-6AA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-6AA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)220.5A
Voltage typeAC
Rated operating frequency50Hz
4EU2722-6AA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)174W
Power loss, iron core (W)85W
Rated ambient temperature40°C
4EU2722-6AA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-6AA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-6AA00-0AA0 is a 3-phase commutating choke (line reactor) designed for converter front ends, rated at 162 A continuous with a 180 A maximum through the same winding. It operates at 500 V AC, 50 Hz, and carries a 0.2 mH inductance with a 4% relative inductive voltage drop — that 4% figure is what governs the choke's sizing for harmonic attenuation and di/dt limiting in a drive input stage. The part is IP00 — open-frame, no enclosure — so it mounts inside a cabinet where the panel builder provides the physical protection. Thermal class H (180 °C insulation system) means it handles the 174 W coil loss plus 85 W iron core loss without derating at the 40 °C ambient rating. Termination is via flat-type connectors (bus-bar or cable lug interface), not screw clamps — factor that into the bus-bar drilling pattern if you're swapping from a different brand's choke.

Physical footprint: 0.27 m wide, 0.248 m tall, 0.187 m deep. Panel layout needs to clear those dimensions plus the flat-connector projection for the main circuit terminals. The 3-phase winding is a single magnetic assembly — no separable cores — so plan for a single mounting footprint, not three separate chokes.

Frequently asked questions

What are the key ratings for 4EU2722-6AA00-0AA0?

Rated 162 A continuous, 180 A maximum, 500 V AC, 3-phase, 50 Hz, 0.2 mH inductance, 4% voltage drop. Thermal class H, IP00, flat-type terminals.

How do I get current pricing and availability for 4EU2722-6AA00-0AA0?

Submit an RFQ through this listing. We source it through independent distribution and confirm availability and current pricing at quote time — no automated stock figure here, just a real quote.

MPN
4EU2722-6AA00-0AA0