Skip to main content
Siemens 4EU2732-0DD08-0BA0 — Line/Load Reactors

SIDAC 4EU2732-0DD08-0BA0 Filter Reactor, 42.8A, 690V, 3-Phas

MPN4EU2732-0DD08-0BA0

SIDAC 4EU2732-0DD08-0BA0 filter reactor, 3-phase, 42.8 A rated current, 690 V AC, 50 Hz, 7 % relative throttling factor, IP00, screw/flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2732-0DD08-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0023H
Relative throttling factor7%
Filter resonant frequency189Hz
Rated reactive power (filter bank)50 000var
4EU2732-0DD08-0BA0 — Identification
ParameterValue
Product designationfilter reactor
4EU2732-0DD08-0BA0 — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2732-0DD08-0BA0 — Losses & Thermal
ParameterValue
Total power loss (W)205W
Rated ambient temperature40°C
4EU2732-0DD08-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2732-0DD08-0BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

What this reactor does in the drive line

The SIDAC 4EU2732-0DD08-0BA0 is a 3-phase filter reactor rated for 42.8 A continuous with a 47.5 A maximum, designed to sit between the drive and the motor or the line supply and the drive. Its 690 V AC operating voltage and 50 Hz rating match standard European industrial mains. The 7 % relative throttling factor means it drops roughly 7 % of line voltage at rated current — enough to limit harmonic distortion and reduce dv/dt stress on motor windings without excessive voltage loss. The 0.0023 H inductance and 189 Hz resonant frequency are tuned for typical PWM drive output, not 50 Hz line filtering alone. At 205 W power loss at full load, this reactor dissipates heat into the enclosure. IP00 means no housing — it needs to be mounted inside a panel with adequate ventilation or forced air, not in a washdown or dust-tight cabinet. Thermal class H (180 °C insulation) gives headroom for the internal temperature rise above the 40 °C ambient rating.

Sizing and fit for a 690 V drive line

Mounting footprint: 0.27 m wide, 0.248 m tall, 0.187 m deep. Screw/flat-type terminals for main circuit; 50 kvar reactive power handling. This is not a DIN-rail component. It bolts directly to the panel structure. The IP00 rating means the installer must maintain clearance to grounded metal and provide finger-safe shrouding if the panel is accessible to non-skilled personnel.

Frequently asked questions

What are the key electrical ratings of 4EU2732-0DD08-0BA0?

Rated current 42.8 A, maximum 47.5 A, operating voltage 690 V AC, 50 Hz, 3-phase, 7 % relative throttling factor, inductance 0.0023 H, resonant frequency 189 Hz, reactive power 50 kvar.

What is the physical size of 4EU2732-0DD08-0BA0?

Width 0.27 m, height 0.248 m, depth 0.187 m. It is a panel-mount reactor, not DIN-rail.

What protection class and terminals does 4EU2732-0DD08-0BA0 have?

IP00 protection class with screw/flat-type terminals for the main circuit connection.

MPN
4EU2732-0DD08-0BA0