Skip to main content
Siemens 4EU2732-0EA30-1B — Line/Load Reactors

Siemens SIDAC 4EU2732-0EA30-1B Filter Reactor, 72A, 480V, 50

MPN4EU2732-0EA30-1B

Siemens SIDAC series, filter reactor, order code 4EU2732-0EA30-1B, 3-phase, 72 A rated / 80 A max, 480 V AC, 50 Hz, 50 kvar, 5.67 % relative throttling, Class H insulation, IP00, flat connector / screw-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2732-0EA30-1B — Inductance & Impedance
ParameterValue
Rated inductance0.00088H
Relative throttling factor5.67%
Filter resonant frequency210Hz
Rated reactive power (filter bank)50 000var
4EU2732-0EA30-1B — Identification
ParameterValue
Product designationfilter reactor
4EU2732-0EA30-1B — Electrical
ParameterValue
Rated operating voltage480V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2732-0EA30-1B — Losses & Thermal
ParameterValue
Total power loss (W)245W
Rated ambient temperature40°C
4EU2732-0EA30-1B — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2732-0EA30-1B — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens SIDAC 4EU2732-0EA30-1B is a 3-phase filter reactor rated for 72 A continuous with an 80 A maximum, designed for 480 V AC line operation at 50 Hz. It delivers 50 kvar of reactive power compensation with a relative throttling factor of 5.67% and an inductance of 0.88 mH. The Class H insulation (180°C thermal class per IEC 60085) means the winding can handle sustained elevated temperatures inside a closed panel without accelerated aging — that's the rating that governs real-world duty in a warm enclosure, not just the ambient 40°C figure.

The 72 A rated current and 80 A maximum tell you the continuous thermal limit and the short-term overload ceiling. The 5.67% impedance attenuates line notches and limits inrush current. The 210 Hz resonant frequency suppresses the 5th harmonic and above. The IP00 protection class means it's an open-frame component — no enclosure, no drip shield. It mounts inside a cabinet, not on the wall. The flat connector / screw-type terminals accept busbar or cable lugs; plan for a separate terminal block if you need ring-tongue terminations. Dimensions are 0.27 m wide by 0.248 m tall by 0.187 m deep — that's about the footprint of a small contactor, but the 245 W power loss at full load means it needs ventilation clearance around it inside the panel. Don't bury it between two solid barriers.

MPN
4EU2732-0EA30-1B