Skip to main content
Siemens 4EU2732-0MF08-0AA0 — Line/Load Reactors

SIDAC 4EU2732-0MF08-0AA0 Filter Reactor, 71A, 415V, 50 kvar

MPN4EU2732-0MF08-0AA0

SIDAC 4EU2732-0MF08-0AA0, 3-phase filter reactor, 71 A rated, 415 V AC, 50 Hz, 50 kvar, 7 % throttling factor, IP00, flat/screw terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU2732-0MF08-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00083H
Relative throttling factor7%
Filter resonant frequency189Hz
Rated reactive power (filter bank)50 000var

Identification

4EU2732-0MF08-0AA0 — Identification
ParameterValue
Product designationfilter reactor

Electrical

4EU2732-0MF08-0AA0 — Electrical
ParameterValue
Rated operating voltage415V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EU2732-0MF08-0AA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C

Approvals

4EU2732-0MF08-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU2732-0MF08-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

What this filter reactor does and where it fits

The SIDAC 4EU2732-0MF08-0AA0 is a 3-phase filter reactor rated for 71 A continuous (78.9 A maximum) at 415 V AC, 50 Hz, delivering 50 kvar of reactive power. The 7 % relative throttling factor and 0.83 mH inductance are sized to suppress harmonic currents from variable-frequency drives and other non-linear loads, protecting upstream capacitors and transformers. The 189 Hz resonant frequency means it's tuned for the 3rd and 5th harmonic range typical of 6-pulse rectifiers. With IP00 protection, this is an open-frame component intended for installation inside a ventilated enclosure or panel — not for washdown or outdoor exposure. Thermal class H insulation (rated for 180 °C continuous) gives headroom in high-ambient cabinets up to 40 °C.

Termination and panel integration

Main circuit connections use flat-type terminals with screw clamping — typical for busbar or cable-lug termination in power distribution panels. The 0.27 m width and 0.248 m height footprint fits a standard sub-panel or backplate layout; the 0.187 m depth must be accounted for in enclosure depth clearance, especially when mounted near gland plates or door-mounted components. IP00 means no ingress protection — keep clearance from live parts per local wiring regulations and ensure the enclosure provides the required IP rating for the environment.

MPN