Skip to main content
Siemens 4EU2732-3MB08-0AA0 — Line/Load Reactors

Siemens SIDAC 4EU2732-3MB08-0AA0 Filter Reactor, 83 A, 400 V

MPN4EU2732-3MB08-0AA0

Siemens SIDAC filter reactor, 3-phase, 400 V AC, 83 A rated (92.2 A max), 0.51 mH, 5.67% impedance, 50 kvar, IP00, screw/flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU2732-3MB08-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00051H
Relative throttling factor5.67%
Filter resonant frequency252Hz
Rated reactive power (filter bank)50 000var

Identification

4EU2732-3MB08-0AA0 — Identification
ParameterValue
Product designationfilter reactor

Electrical

4EU2732-3MB08-0AA0 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Voltage typeAC
Rated operating frequency60Hz

Losses & Thermal

4EU2732-3MB08-0AA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C

Approvals

4EU2732-3MB08-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU2732-3MB08-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

Line reactor for 400 V AC drives — 83 A continuous, 92.2 A peak

The Siemens SIDAC 4EU2732-3MB08-0AA0 is a 3-phase filter reactor rated for 83 A continuous (92.2 A maximum) at 400 V AC, 60 Hz. The 0.51 mH inductance with a 5.67% relative throttling factor places it squarely in the line-reactor class for variable-frequency drive input circuits — it smooths current harmonics and limits di/dt on the DC bus. The 50 kvar reactive power rating tells you the reactive compensation it can handle; the 252 Hz resonant frequency means it's tuned to suppress harmonics around the 5th (300 Hz at 60 Hz fundamental), which is the dominant harmonic from a 6-pulse rectifier. IP00 means no enclosure — this mounts inside a panel, not in a washdown zone.

Sizing and fit — what the 83 A / 92.2 A split means

The 83 A rated value is the continuous thermal current under the rated ambient of 40 °C. The 92.2 A maximum is the overload ceiling before the Class H insulation starts degrading.

Panel integration — dimensions and terminals

The reactor measures 0.187 m deep by 0.27 m wide by 0.248 m tall. The main circuit connections are flat connector / screw-type terminals.

Frequently asked questions

What is the physical size of 4EU2732-3MB08-0AA0?

Depth 0.187 m, width 0.27 m, height 0.248 m. IP00 protection class — no enclosure, for panel-mount use only.

MPN
4EU2732-3MB08-0AA0