The SIDAC 4EU2752-0EF00-4BA0 is a 3-phase AC output reactor (output choke) rated for 80 A maximum continuous current and a switching frequency of 8 kHz. Its 0.1 mH inductance limits the rate of current rise from the drive output, protecting motor windings and cable insulation from the voltage spikes that PWM drives produce. The 160 W coil loss and 130 W iron core loss at rated load tell you the thermal load this reactor dumps into the enclosure — plan for that heat. The reactor is rated for a 40 °C ambient and carries thermal class H insulation per IEC 60085, meaning the winding can handle a 180 °C hot-spot temperature without degrading. That gives you margin if the panel runs warm or the motor cable is long.
This is an IP00 open-frame reactor — no enclosure, no drip shield. It mounts inside a panel or cabinet where the ambient stays clean and dry. The main circuit terminates on flat-type connectors (bus-bar style), so you'll need a mating flat tab or a compression lug; no screw-clamp terminals here. Dimensions are 0.27 m wide by 0.24 m tall by 0.18 m deep — about the size of a small shoebox. Plan the panel layout so the reactor sits close to the drive output to keep the motor cable as short as possible on the line side.