Skip to main content
Siemens 4EU2752-0ER00-0BA0 — Line/Load Reactors

Siemens 4EU2752-0ER00-0BA0 Mains Choke, 260A, 400V, 3-Phase

MPN4EU2752-0ER00-0BA0

Siemens 4EU2752-0ER00-0BA0, Netzdrossel mains choke, 3-phase AC, 400V rated voltage, 260A rated current (289A max), 0.15mH inductance, IP00, thermal class H, EN 61558-2-20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2752-0ER00-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00015H
Relative inductive voltage drop7.2%
4EU2752-0ER00-0BA0 — Identification
ParameterValue
Product designationNetzdrossel
4EU2752-0ER00-0BA0 — Electrical
ParameterValue
Rated operating voltage400, 400V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU2752-0ER00-0BA0 — Losses & Thermal
ParameterValue
Rated ambient temperature45°C
4EU2752-0ER00-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2752-0ER00-0BA0 — Mechanical
ParameterValue
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.208m
4EU2752-0ER00-0BA0 — Other specifications
ParameterValue
Rated value260A

Product details

The Siemens 4EU2752-0ER00-0BA0 is a three-phase mains choke (Netzdrossel) rated for 400 V AC line voltage, 260 A continuous current with a 289 A maximum, and 0.15 mH inductance. It's built to EN 61558-2-20 for power transformers and reactors — the standard that governs thermal and dielectric endurance under load.

Key ratings and their meaning

The 260 A rated current (289 A maximum) is the continuous thermal limit under the rated 45°C ambient — push beyond that and the Class H insulation (180°C rated, per IEC 60085) still gives headroom, but the voltage drop across the choke climbs. That drop is measured at the fundamental frequency; it's higher for harmonic currents, which is exactly what the choke is there to suppress.

Physical footprint: 0.27 m wide, 0.248 m tall, 0.208 m deep. That's a substantial block — plan for a DIN-rail or baseplate mount inside a cabinet with enough clearance for airflow. The IP00 rating means no touch protection on the terminals; the enclosing panel must provide the IP2X or better. Thermal class H allows a 180°C hot-spot, so forced ventilation or a larger enclosure may be needed if ambient inside the panel exceeds 45°C.

Frequently asked questions

What are the key electrical ratings for this mains choke?

Rated current 260 A, maximum current 289 A, rated voltage 400 V AC, 3-phase, inductance 0.15 mH, operating frequency 50 to 60 Hz, relative inductive voltage drop 7.2 % at rated conditions.

What compliance standard does 4EU2752-0ER00-0BA0 meet?

It complies with EN 61558-2-20, the European standard for power transformers and reactors covering thermal and dielectric endurance. Thermal class H per IEC 60085 (rated 180 °C).

Where can I buy 4EU2752-0ER00-0BA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here.

MPN
4EU2752-0ER00-0BA0