Skip to main content
Siemens 4EU2752-2UA00-0AA0 — Line/Load Reactors

Siemens 4EU2752-2UA00-0AA0 Mains Choke, 3-Phase, 250A, 500V

MPN4EU2752-2UA00-0AA0

Siemens Netzdrossel f. FU, 4EU2752-2UA00-0AA0, 3-phase AC mains choke, 500V rated, 250A max, 73µH, IP00, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU2752-2UA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000073H
Relative inductive voltage drop2%
4EU2752-2UA00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2752-2UA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)225A
Number of phases3
Current (AC), max.250A
Voltage typeAC
Rated operating frequency50Hz
4EU2752-2UA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)179W
Power loss, iron core (W)58W
Rated ambient temperature40°C
4EU2752-2UA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2752-2UA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.208m

Product details

The Siemens 4EU2752-2UA00-0AA0 is a three-phase mains choke (line reactor) designed for the input of a frequency converter (FU). It sits between the supply and the drive, limiting harmonic current, reducing voltage notching, and protecting the DC bus from line transients. The 73 µH inductance and 2% relative inductive voltage drop are tuned for typical drive input filtering — enough to smooth commutation notches without dropping excessive voltage under load. IP00 open-frame construction means it goes inside a panel or enclosure, not exposed.

Thermal and insulation class

Rated at 40 °C ambient with thermal class H (IEC 60085) — the winding insulation handles 180 °C hot-spot temperature. Total power loss splits 179 W in the coil and 58 W in the iron core at rated load, so the enclosure must move 237 W of heat. That is a real thermal budget for a panel builder: at 250 A continuous, forced ventilation or a larger cabinet is likely required.

UL/CSA recognized (per EN 61558-2-20) — the nameplate carries the mark, so panel shops in North America can accept it without separate agency review.

Frequently asked questions

What compliance documentation does this choke carry?

It is UL/CSA recognized under EN 61558-2-20. The flat-type terminals and IP00 rating are part of the construction standard.

MPN
4EU2752-2UA00-0AA0