Skip to main content
Siemens 4EU2752-2UB00-0AA0 — Line/Load Reactors

Siemens 4EU2752-2UB00-0AA0 Mains Choke, 3-Phase, 200 A, 0.14

MPN4EU2752-2UB00-0AA0

Siemens 4EU2752-2UB00-0AA0 mains choke (Netzdrossel f. FU), 3-phase AC, 400/480 V, 200 A max, 0.14 mH, 4% voltage drop, IP00, class H insulation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2752-2UB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00014H
Relative inductive voltage drop4%
4EU2752-2UB00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2752-2UB00-0AA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)180A
Number of phases3
Current (AC), max.200A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU2752-2UB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)172W
Power loss, iron core (W)87W
Rated ambient temperature40°C
4EU2752-2UB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2752-2UB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.208m

Product details

The Siemens 4EU2752-2UB00-0AA0 is a three-phase mains choke (Netzdrossel f. FU) sized for frequency converter input lines. It handles 200 A maximum at 400/480 V AC, 50/60 Hz, with a rated inductance of 0.14 mH and a 4% relative inductive voltage drop. That 4% figure is the design target — it limits harmonic current without dragging the DC bus voltage down too far under load.

The 180 A operational current is the continuous rating at the 40 °C ambient — that's the number to match against your drive's input current, not the 200 A thermal maximum which is a short-time overload ceiling. The 172 W coil loss plus 87 W iron loss add up to about 259 W of heat to vent inside the enclosure; IP00 means it's open-frame, so it needs cabinet space with forced airflow or natural convection paths clear on all sides. Class H insulation per IEC 60085 means the winding can sustain 180 °C hot-spot temperature — that's a step above the usual class F (155 °C) found on economy chokes, so it holds up better in a crowded panel or a warm machine room.

Main circuit connections are flat-type terminals — expect bus-bar or crimp-on ring lugs, not screw-clamp wire entry. The footprint is 0.27 m wide by 0.248 m tall by 0.208 m deep; that's about 10.6 by 9.8 by 8.2 inches. No DIN-rail clip — it's a bolt-down chassis mount, so plan for a sub-panel or mounting plate.

Frequently asked questions

How do I get current pricing and availability for 4EU2752-2UB00-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What are the key electrical ratings of 4EU2752-2UB00-0AA0?

Three-phase AC, 400/480 V, 50/60 Hz, 200 A maximum current, 180 A operational current at 40 °C ambient, 0.14 mH inductance, 4% voltage drop, class H insulation.

What compliance documentation does Siemens provide for 4EU2752-2UB00-0AA0?

The part is recognized under UL/CSA per the description and designed to EN 61558-2-20. RoHS/REACH documentation is typically available from Siemens on request.

MPN
4EU2752-2UB00-0AA0