Siemens 4EU3022-0EF00-0AA0 — Line/Load Reactors

Siemens 4EU3022-0EF00-0AA0 Mains Choke, 3-Phase, 400V, 100.8

MPN4EU3022-0EF00-0AA0

Siemens SENTRON 4EU3022-0EF00-0AA0 mains choke for frequency converters, 3-phase, 400V AC, rated current 100.8A (max 112A), 0.395 mH, 6% voltage drop, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3022-0EF00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0004H
Relative inductive voltage drop6%
4EU3022-0EF00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3022-0EF00-0AA0 — Electrical
ParameterValue
Rated operating voltage0, 400V
Number of phases3
Voltage typeAC
Rated operating frequency0 ... 50Hz
4EU3022-0EF00-0AA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU3022-0EF00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3022-0EF00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.221m
4EU3022-0EF00-0AA0 — Other specifications
ParameterValue
Rated value100.8A

Product details

The Siemens 4EU3022-0EF00-0AA0 is a three-phase mains choke (line reactor) designed for the input side of variable frequency drives. It smooths current harmonics and limits inrush, protecting both the drive and the upstream supply. Rated for 400 V AC, it carries a maximum continuous current of 112 A and a rated current of 100.8 A at 50 Hz — the 6% voltage drop at rated conditions is the design target for typical drive input filtering.

The 100.8 A rated current (112 A max) tells you this choke is sized for a drive with a comparable input current rating — oversizing by more than a frame risks losing the harmonic attenuation, undersizing cooks the winding. The 0.395 mH inductance (0.0004 H) and 6% voltage drop are paired; a different impedance changes the filtering curve. Thermal class H (180 °C insulation) means the winding can survive sustained overloads that would cook a class B or F choke — relevant if your drive cycles hard or runs near a hot panel wall. IP00 means no enclosure — this choke mounts inside a cabinet, not in a washdown area. The flat-type terminals accept busbar or cable lugs; plan for a 0.3 m width and 0.221 m depth on the mounting surface.

This is a panel-mounted component, not DIN-rail. The 0.3 m width and 0.269 m height footprint needs a backplate or sub-panel; the 0.221 m depth projects into the cabinet, so check your enclosure depth before committing. Flat-type terminals suit busbar connection or ring-tongue lugs — no spring-cage or screw-clamp here. Mount it between the supply disconnect and the drive input; keep power wiring short to minimize radiated noise.

Frequently asked questions

Where can I buy 4EU3022-0EF00-0AA0 and get a price?

This part is sourced to order through independent distribution against an RFQ. Submit a request for quote; availability and current pricing are confirmed at quote time.

What are the key specifications of 4EU3022-0EF00-0AA0?

It is a 3-phase mains choke rated 400 V AC, 100.8 A (max 112 A), 0.395 mH inductance, 6% voltage drop, IP00, thermal class H, with flat-type terminals.

What is the physical size of 4EU3022-0EF00-0AA0?

The dimensions are 0.3 m width, 0.269 m height, and 0.221 m depth.

MPN
4EU3022-0EF00-0AA0