Skip to main content
Siemens 4EU3022-0EH00-1BA0 — Line/Load Reactors

Siemens 4EU3022-0EH00-1BA0 Commutating Choke, 327A, 3-Phase

MPN4EU3022-0EH00-1BA0

Siemens 4EU3022-0EH00-1BA0, 3-phase commutating choke for converters, 400V AC, 294.3A rated / 327A max, 0.09 mH, IP00, flat-type terminals, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3022-0EH00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00009H
Relative inductive voltage drop4%
4EU3022-0EH00-1BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3022-0EH00-1BA0 — Electrical
ParameterValue
Rated operating voltage400, 400V
Number of phases3
Rated current (DC)400.7A
Voltage typeAC
Rated operating frequency60 ... 50Hz
4EU3022-0EH00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)205W
Power loss, iron core (W)160W
Rated ambient temperature50°C
4EU3022-0EH00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3022-0EH00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

The Siemens 4EU3022-0EH00-1BA0 is a 3-phase commutating choke (German designation: Kommut.-Drossel f. Stromrichter) designed for line-commutated converters. It sits between the AC supply and the converter input to limit the rate of rise of fault current and reduce harmonic distortion on the line side. Rated for 294.3 A continuous with a maximum short-time rating of 327 A at 60 Hz, this choke handles the current ripple and commutation notches a 6-pulse or 12-pulse drive throws back at the mains.

The 294.3 A rated current is the continuous thermal current at the 50 °C ambient temperature rating. The 327 A maximum is the overload capability at 60 Hz — this is not a continuous rating; it's the peak the choke can sustain briefly during a converter fault or inrush event. The 0.09 mH inductance with a 4% relative inductive voltage drop means the choke presents about 4% of the line voltage as inductive drop at rated current — a standard value for commutating chokes that keeps the DC-link voltage drop within acceptable limits for most drives. The 400 V AC operating voltage matches standard 400 V three-phase industrial mains. Thermal class H means the insulation system is rated for 180 °C hot-spot temperature — this choke can live inside a warm cabinet without derating, as long as the ambient stays at or below 50 °C.

This is a panel-mount component — IP00 means no enclosure protection, so it must be installed inside a cabinet with at least IP2X protection. The flat-type terminals accept busbar or cable lug connections typical of larger power components. Dimensions are 0.3 m wide × 0.269 m high × 0.211 m deep — plan for a footprint roughly 300 × 270 mm on the mounting plate, plus clearance for airflow. The 205 W coil loss plus 160 W iron core loss totals 365 W of heat to vent out of the enclosure; factor that into the cabinet cooling calculation.

Frequently asked questions

Where can I buy 4EU3022-0EH00-1BA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time.

What are the key dimensions for panel layout?

The choke measures 0.3 m wide × 0.269 m high × 0.211 m deep. Plan for a 300 × 270 mm mounting footprint plus clearance for airflow and flat-type terminal connections.

What compliance documentation is available for 4EU3022-0EH00-1BA0?

The part carries a declaration of conformity to EN 61558-2-20 (safety of transformers, reactors, and power supply units) as noted in the description. Standard Siemens documentation includes the CE declaration; specific RoHS/REACH status should be confirmed at quote time as it varies by production batch.

MPN
4EU3022-0EH00-1BA0