Skip to main content
Siemens 4EU3022-4AA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-4AA00-0AA0 Commutating Choke, 225A, 500V, 0.

MPN4EU3022-4AA00-0AA0

Siemens 4EU3022-4AA00-0AA0 commutating choke for converter applications, 3-phase, 225 A rated current, 500 V AC, 0.15 mH inductance, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3022-4AA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00015H
Relative inductive voltage drop4%
4EU3022-4AA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3022-4AA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)306.3A
Voltage typeAC
Rated operating frequency50Hz
4EU3022-4AA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)220W
Power loss, iron core (W)148W
Rated ambient temperature40°C
4EU3022-4AA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3022-4AA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

The Siemens 4EU3022-4AA00-0AA0 is a three-phase commutating choke (line reactor) designed for converter front-ends. It carries a rated current of 225 A and a maximum current of 250 A at 50 Hz, with an inductance of 0.15 mH and a relative inductive voltage drop of 4% at rated conditions. The 500 V AC operating voltage suits 400 V class drives and converters where additional line impedance is needed to limit harmonic distortion and reduce peak currents.

The 225 A rated current (250 A maximum) is the continuous thermal current at 40 °C ambient — sized for a 200–250 A drive input. The 0.15 mH inductance at 50 Hz provides a 4% impedance drop, which is typical for line reactors used to attenuate harmonics and protect the DC bus from line notching. The DC-rated current of 306.3 A indicates the choke can also handle DC-side ripple current if used in a DC-link configuration, though the primary application is AC line-side commutation. Power loss is split: 220 W in the coil and 148 W in the iron core, totaling 368 W at rated load. This heat must be dissipated; the IP00 enclosure means no fan or filter — the choke relies on natural convection in a clean, dry cabinet. Thermal class H (180 °C insulation system) per IEC 60085 gives headroom for sustained overloads up to the thermal limit.

Mounts on a panel or chassis via the flat-type terminals for the main circuit — no DIN-rail clip. Dimensions are 0.3 m wide × 0.269 m high × 0.211 m deep, so it occupies roughly the footprint of a small suitcase. The IP00 rating means it is not sealed; install it inside a cabinet that keeps out dust and moisture. The flat terminals accept busbar or cable lugs, common for this current class.

Frequently asked questions

What is the physical size of 4EU3022-4AA00-0AA0?

Width 0.3 m, height 0.269 m, depth 0.211 m. It uses flat-type terminals for the main circuit and is rated IP00.

MPN
4EU3022-4AA00-0AA0