Skip to main content
Siemens 4EU3022-5AA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-5AA00-0AA0 Commutating Choke, 252 A, 3-Phase

MPN4EU3022-5AA00-0AA0

Siemens 4EU3022-5AA00-0AA0, commutating choke for converter, 3-phase, 500 V AC, 50 Hz, rated 252 A, maximum 280 A, IP00, thermal class H, flat-type terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3022-5AA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value500V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil210W
Power loss [W] of the iron core143W
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.211m
Width0.3m
Height0.269m
Thermal class acc. to IEC 60085H
Rated value252A
At DC rated value343.1A
Protection class IPIP00
Inductivity rated value0.00013H

Product details

The Siemens 4EU3022-5AA00-0AA0 is a 3-phase commutating choke (drossel) designed for converter output circuits. The 0.13 mH inductance limits the rate of current rise during commutation, protecting the converter's power semiconductors from di/dt stress.

The 252 A rated value (I_LN) is the continuous current the choke can handle at its 40 °C ambient rating. The 280 A maximum (I_thmax) is the thermal limit under overload — useful for sizing against short-duration peaks in a drive cycle. At DC, the same choke is rated 343.1 A, reflecting the lower RMS heating of DC current vs AC. The 4 % relative inductive voltage drop (u_k) tells you the voltage the choke consumes at rated current; factor this into the drive's available output voltage budget. Thermal class H (180 °C) insulation means the choke can run hot without degrading the winding — important for enclosed panels where airflow is limited. The 210 W coil loss plus 143 W iron core loss (353 W total) must be dissipated; plan for that heat load in your enclosure cooling calculation.

This choke mounts between the converter output and the motor, typically on a sub-panel or chassis baseplate — IP00 means no enclosure protection, so it requires a cabinet. The flat-type terminals accept busbar or cable lugs; plan for 0.211 m depth, 0.3 m width, 0.269 m height when laying out the panel. It is designed for 50 Hz operation; verify compatibility if your drive runs at 60 Hz output.

Frequently asked questions

Where can I buy 4EU3022-5AA00-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key dimensions of 4EU3022-5AA00-0AA0?

The choke measures 0.211 m depth, 0.3 m width, and 0.269 m height. These are the physical envelope dimensions for panel layout.

What compliance documentation is available for 4EU3022-5AA00-0AA0?

The evidence does not list RoHS, REACH, UL, or IEC certificates for this specific order code. Request compliance documentation at RFQ time.

MPN
4EU3022-5AA00-0AA0