Siemens 4EU3022-6CA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-6CA00-0AA0 Commutating Choke, 224A, 0.25mH

MPN4EU3022-6CA00-0AA0

Siemens 4EU3022-6CA00-0AA0 commutating choke for converter, 3-phase, 750V AC, 224A max / 201.6A rated, 0.25mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3022-6CA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value0, 750V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil208W
Power loss [W] of the iron core151W
Operating frequency rated value0 ... 50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.211m
Width0.3m
Height0.269m
Thermal class acc. to IEC 60085H
Rated value201.6A
At DC rated value274.5A
Protection class IPIP00
Inductivity rated value0.00025H

Product details

The Siemens 4EU3022-6CA00-0AA0 is a 3-phase commutating choke — a line reactor — designed for the DC link of a converter or drive. It smooths current ripple and limits di/dt during commutation, which protects the converter's semiconductor switches and reduces harmonic distortion feeding back to the line. Rated for a continuous current of 201.6 A (224 A maximum) at 750 V AC, 50 Hz, with an inductance of 0.00025 H.

IP00 open-frame construction means this choke has no enclosure — it mounts inside a panel or cabinet where the ambient stays clean and dry. The flat-type terminals accept bus-bar or heavy cable lugs; plan for bolted connections, not spring-clamp wiring. Footprint measures 0.3 m wide by 0.211 m deep by 0.269 m tall. Combined copper and iron losses total 208 W plus 151 W.

Thermal class and operating conditions

Rated for a 40 °C ambient with Class H insulation per IEC 60085 — that's a 180 °C hot-spot limit, so it can handle sustained overloads and high ambient temperatures inside a crowded panel without derating prematurely. The DC-rated current is 274.5 A — useful if you're applying it in a DC-link circuit rather than the AC line side. The 0–50 Hz operating frequency covers standard 50 Hz mains and variable-frequency drive output up to 50 Hz.

MPN