Skip to main content
Siemens 4EU3022-8AA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-8AA00-0AA0 Commutating Choke, 224A, 690V, 3-

MPN4EU3022-8AA00-0AA0

Siemens 4EU3022-8AA00-0AA0 commutating choke (drossel) for converter, 3-phase, 224A maximum / 201.6A rated, 690V AC, 0.22 mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3022-8AA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value690, 690V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil220W
Power loss [W] of the iron core160W
Operating frequency rated value60 ... 50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.211m
Width0.3m
Height0.269m
Thermal class acc. to IEC 60085H
Rated value201.6A
At DC rated value274.5A
Protection class IPIP00
Inductivity rated value0.00022H

Product details

The Siemens 4EU3022-8AA00-0AA0 is a 3-phase commutating choke (drossel) for converter applications, rated for 224 A maximum and 201.6 A continuous at 690 V AC, 50/60 Hz. The 0.22 mH inductance with a 4% relative inductive voltage drop limits current rise and harmonics on the converter's DC link or input side. Thermal class H (180 °C) insulation and a 40 °C ambient rating mean it handles sustained converter duty without derating in a typical enclosed cabinet — provided the enclosure moves enough air to clear 220 W coil losses plus 160 W iron losses.

Sizing and thermal reality

The 201.6 A rated current (I LN) is the continuous figure for a 690 V, 3-phase converter line. The 224 A maximum (ITHMAX 1) is the thermal limit at 50 Hz — use the 201.6 A figure for BOM sizing unless the duty cycle is demonstrably intermittent. The 220 W coil loss plus 160 W iron core loss sum to 380 W dissipated inside the choke; at IP00 with no enclosure, that's fine, but panel builders need to account for that heat rise in the cabinet thermal budget.

Mounting and connection

The 0.3 m width, 0.269 m height, and 0.211 m depth define the footprint for panel layout. IP00 means no ingress protection — the choke must be mounted inside a cabinet that provides the environmental seal. Connections are via flat-type terminals (flat connector) for the main current circuit, sized for the 224 A path. No DIN-rail clip; expect bolt-through or bracket mounting to a backplate.

Frequently asked questions

What are the key ratings for the 4EU3022-8AA00-0AA0?

3-phase commutating choke rated 224 A maximum, 201.6 A continuous, 690 V AC, 0.22 mH inductance, 4% voltage drop, thermal class H, IP00, with flat-type terminals.

Where can I buy the 4EU3022-8AA00-0AA0?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability; the quote will confirm the supply position at that time.

What is the physical size of the 4EU3022-8AA00-0AA0?

Width 0.3 m, height 0.269 m, depth 0.211 m. IP00, so it requires enclosure mounting.

MPN