Skip to main content
Siemens 4EU3022-8AA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-8AA00-0AA0 Commutating Choke, 224A, 690V, 3-

MPN4EU3022-8AA00-0AA0

Siemens 4EU3022-8AA00-0AA0 commutating choke (drossel) for converter, 3-phase, 224A maximum / 201.6A rated, 690V AC, 0.22 mH, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3022-8AA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00022H
Relative inductive voltage drop4%

Identification

4EU3022-8AA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU3022-8AA00-0AA0 — Electrical
ParameterValue
Rated operating voltage690, 690V
Number of phases3
Rated current (DC)274.5A
Voltage typeAC
Rated operating frequency60 ... 50Hz

Losses & Thermal

4EU3022-8AA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)220W
Power loss, iron core (W)160W
Rated ambient temperature40°C

Approvals

4EU3022-8AA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3022-8AA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

The Siemens 4EU3022-8AA00-0AA0 is a 3-phase commutating choke (drossel) for converter applications, rated for 224 A maximum and 201.6 A continuous at 690 V AC, 50/60 Hz. The 0.22 mH inductance with a 4% relative inductive voltage drop limits current rise and harmonics on the converter's DC link or input side. Thermal class H (180 °C) insulation and a 40 °C ambient rating mean it handles sustained converter duty without derating in a typical enclosed cabinet — provided the enclosure moves enough air to clear 220 W coil losses plus 160 W iron losses.

Sizing and thermal reality

The 201.6 A rated current (I LN) is the continuous figure for a 690 V, 3-phase converter line. The 224 A maximum (ITHMAX 1) is the thermal limit at 50 Hz — use the 201.6 A figure for BOM sizing unless the duty cycle is demonstrably intermittent. The 220 W coil loss plus 160 W iron core loss sum to 380 W dissipated inside the choke; at IP00 with no enclosure, that's fine, but panel builders need to account for that heat rise in the cabinet thermal budget.

Mounting and connection

The 0.3 m width, 0.269 m height, and 0.211 m depth define the footprint for panel layout. IP00 means no ingress protection — the choke must be mounted inside a cabinet that provides the environmental seal. Connections are via flat-type terminals (flat connector) for the main current circuit, sized for the 224 A path. No DIN-rail clip; expect bolt-through or bracket mounting to a backplate.

Frequently asked questions

What are the key ratings for the 4EU3022-8AA00-0AA0?

3-phase commutating choke rated 224 A maximum, 201.6 A continuous, 690 V AC, 0.22 mH inductance, 4% voltage drop, thermal class H, IP00, with flat-type terminals.

Where can I buy the 4EU3022-8AA00-0AA0?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability; the quote will confirm the supply position at that time.

What is the physical size of the 4EU3022-8AA00-0AA0?

Width 0.3 m, height 0.269 m, depth 0.211 m. IP00, so it requires enclosure mounting.

MPN
4EU3022-8AA00-0AA0