Skip to main content
Siemens 4EU3022-8BA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-8BA00-0AA0 Commutating Choke, 224A, 690V

MPN4EU3022-8BA00-0AA0

Siemens 4EU3022-8BA00-0AA0 commutating choke, 3-phase, 690V AC, 224A max / 202A rated, 0.17mH, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3022-8BA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00017H
Relative inductive voltage drop4%

Identification

4EU3022-8BA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU3022-8BA00-0AA0 — Electrical
ParameterValue
Rated operating voltage690, 690V
Number of phases3
Rated current (DC)274.5A
Voltage typeAC
Rated operating frequency60 ... 50Hz
Peak current280A

Losses & Thermal

4EU3022-8BA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)220W
Power loss, iron core (W)110W
Rated ambient temperature40°C

Approvals

4EU3022-8BA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3022-8BA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

What it is and what it does

The Siemens 4EU3022-8BA00-0AA0 is a commutating choke (line reactor) for converter duty, designed to limit di/dt and smooth commutation notches on the AC input of a 3-phase drive or rectifier. It carries a maximum continuous current of 224 A at 50 Hz, with a rated operating current of 202 A and a peak current capability of 280 A. At DC the rated value is 274.5 A, so it also fits DC-link applications where the ripple current stays within the inductor's thermal budget.

Key ratings and what they mean for fit

Rated for 690 V AC line-to-line, with an operating frequency of 50 to 60 Hz — covers standard 400 V and 690 V industrial mains without derating. The 0.17 mH inductance (170 µH) and 4 % relative inductive voltage drop at rated current define the impedance; this is the figure that governs how much harmonic current the choke attenuates. A 4 % drop is typical for a commutating choke — it limits notching without dropping excessive voltage under load. Total power loss is 330 W (220 W coil loss + 110 W iron core loss) at the rated operating point. Thermal class H per IEC 60085 means the insulation system withstands 180 °C hot-spot temperature, so the choke can run hot in a confined cabinet as long as the ambient stays at or below 40 °C. The IP00 enclosure means it is an open-frame component — it must be mounted inside a panel or enclosure that provides the touch-safe and environmental protection.

Mounting and connection

Physical footprint is 0.300 m wide × 0.269 m high × 0.211 m deep. The main circuit connects via flat-type terminals (bus-bar or crimp lug), not screw-clamp or spring-cage — plan for a bus-bar interface or flat-pin female connectors. The choke is a three-phase device (3 phases), so all three line conductors pass through the single core.

Frequently asked questions

Where can I buy 4EU3022-8BA00-0AA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What are the key ratings for 4EU3022-8BA00-0AA0?

It is a 3-phase commutating choke rated 690 V AC, 224 A maximum continuous current (202 A rated), 0.17 mH inductance, with a 4 % inductive voltage drop at rated current. Peak current capability is 280 A.

What compliance documentation is available for 4EU3022-8BA00-0AA0?

The choke is designed to EN 61558-2-20 (safety of transformers, reactors, and power supply units) and carries thermal class H insulation per IEC 60085. Standard Siemens declarations for RoHS and REACH are available on request.

MPN
4EU3022-8BA00-0AA0