Skip to main content
Siemens 4EU3022-8BA00-0AA0 — Line/Load Reactors

Siemens 4EU3022-8BA00-0AA0 Commutating Choke, 224A, 690V

MPN4EU3022-8BA00-0AA0

Siemens 4EU3022-8BA00-0AA0 commutating choke, 3-phase, 690V AC, 224A max / 202A rated, 0.17mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3022-8BA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value690, 690V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Peak current280A
Power loss [W] of the coil220W
Power loss [W] of the iron core110W
Operating frequency rated value60 ... 50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.211m
Width0.3m
Height0.269m
Thermal class acc. to IEC 60085H
Rated value202A
At DC rated value274.5A
Protection class IPIP00
Inductivity rated value0.00017H

Product details

The Siemens 4EU3022-8BA00-0AA0 is a commutating choke (line reactor) for converter duty, designed to limit di/dt and smooth commutation notches on the AC input of a 3-phase drive or rectifier. At DC the rated value is 274.5 A, so it also fits DC-link applications where the ripple current stays within the inductor's thermal budget.

Rated for 690 V AC line-to-line, with an operating frequency of 50 to 60 Hz — covers standard 400 V and 690 V industrial mains without derating. A 4 % drop is typical for a commutating choke — it limits notching without dropping excessive voltage under load. Total power loss is 330 W (220 W coil loss + 110 W iron core loss) at the rated operating point. Thermal class H per IEC 60085 means the insulation system withstands 180 °C hot-spot temperature, so the choke can run hot in a confined cabinet as long as the ambient stays at or below 40 °C.

Mounting and connection

Physical footprint is 0.300 m wide × 0.269 m high × 0.211 m deep. The main circuit connects via flat-type terminals (bus-bar or crimp lug), not screw-clamp or spring-cage — plan for a bus-bar interface or flat-pin female connectors. The choke is a three-phase device (3 phases), so all three line conductors pass through the single core.

Frequently asked questions

Where can I buy 4EU3022-8BA00-0AA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What are the key ratings for 4EU3022-8BA00-0AA0?

It is a 3-phase commutating choke rated 690 V AC, 224 A maximum continuous current (202 A rated), 0.17 mH inductance, with a 4 % inductive voltage drop at rated current. Peak current capability is 280 A.

What compliance documentation is available for 4EU3022-8BA00-0AA0?

The choke is designed to EN 61558-2-20 (safety of transformers, reactors, and power supply units) and carries thermal class H insulation per IEC 60085. Standard Siemens declarations for RoHS and REACH are available on request.

MPN
4EU3022-8BA00-0AA0