Skip to main content
Siemens 4EU3032-0AS00-0BA0 — Line/Load Reactors

Siemens SIDAC 4EU3032-0AS00-0BA0 Filter Reactor, 690 V, 85 k

MPN4EU3032-0AS00-0BA0

Siemens SIDAC filter reactor, 3-phase, 690 V AC, 85 kvar, 7% throttling, 50 Hz, IP00, thermal class H, flat/screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3032-0AS00-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0013H
Relative throttling factor7%
Filter resonant frequency189Hz
Rated reactive power (filter bank)85 000var
4EU3032-0AS00-0BA0 — Identification
ParameterValue
Product designationfilter reactor
4EU3032-0AS00-0BA0 — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU3032-0AS00-0BA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU3032-0AS00-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3032-0AS00-0BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

3-phase filter reactor for harmonic mitigation

The Siemens SIDAC 4EU3032-0AS00-0BA0 is a 3-phase filter reactor rated for 690 V AC at 50 Hz, with a reactive power of 85 kvar and a relative throttling factor of 7%. Inductance is 0.0013 H; resonant frequency is 189 Hz. Thermal class H (180 °C) insulation per IEC 60085 means the reactor can operate at elevated ambient temperatures without derating — critical when mounted inside a sealed panel with other heat sources. The flat connector / screw-type terminals accept busbar or cable lugs for the main current circuit.

The 7% throttling factor is the standard impedance for line reactors used with variable-frequency drives — it limits inrush current and reduces harmonic distortion without excessive voltage drop at full load. Reactive power rating is 85 kvar at 690 V. The 0.0013 H inductance is the per-phase value at rated current. This inductance, combined with the 189 Hz resonant frequency, ensures the reactor does not resonate with power-factor correction capacitors at the fundamental or dominant harmonic frequencies.

MPN
4EU3032-0AS00-0BA0