The SIDAC 4EU3032-0EA18-4EA0 is a 3-phase filter reactor rated 69 A continuous (76.9 A maximum) at 400 V AC, 50 Hz, with a reactive power of 50 kvar. The 14% relative throttling factor means the reactor introduces a 14% voltage drop at rated current — a common value for harmonic mitigation in variable-frequency-drive line inputs. The 0.0017 H inductance and 134 Hz resonant frequency are tuned to suppress the 5th and 7th harmonics typical of 6-pulse rectifiers.
Mount this reactor inside a ventilated enclosure — IP00 means no protection against dust ingress or water, so it needs the cabinet to provide the environmental seal. The flat connector / screw-type terminals accept lug or bus-bar connections for the main circuit. Dimensions are 0.3 m wide by 0.269 m tall by 0.211 m deep; verify panel depth clearance before layout. The thermal class H insulation (rated for 180 °C continuous) allows the reactor to run hot in a confined space without derating the winding, but the 40 °C ambient rating is the reference — above that, the core and copper losses must be considered in the thermal design.