Skip to main content
Siemens 4EU3032-0FE08-4BA0 — Line/Load Reactors

Siemens SIDAC 4EU3032-0FE08-4BA0 Filter Reactor, 525V 59.1A

MPN4EU3032-0FE08-4BA0

Siemens SIDAC 4EU3032-0FE08-4BA0, 3-phase filter reactor, 525 V AC, 59.1 A rated, 50 Hz, 50 kvar, IP00, thermal class H, screw/flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3032-0FE08-4BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0025H
Relative throttling factor12.5%
Filter resonant frequency141Hz
Rated reactive power (filter bank)50 000var
4EU3032-0FE08-4BA0 — Identification
ParameterValue
Product designationfilter reactor
4EU3032-0FE08-4BA0 — Electrical
ParameterValue
Rated operating voltage525V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU3032-0FE08-4BA0 — Losses & Thermal
ParameterValue
Total power loss (W)315W
Rated ambient temperature40°C
4EU3032-0FE08-4BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3032-0FE08-4BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

What this reactor does on the line

The Siemens SIDAC 4EU3032-0FE08-4BA0 is a 3-phase filter reactor rated for 525 V AC at 50 Hz, with a rated current of 59.1 A and a maximum current of 65.7 A. Its 0.0025 H inductance and 12.5% relative throttling factor are sized to suppress harmonic currents and limit inrush in drives and power-converter circuits. The 50 kvar reactive-power rating tells you the bank it's designed to work with — match it to a capacitor bank of that size for a detuned filter assembly. The resonant frequency sits at 141 Hz, which places the filter's trap below the 5th harmonic (250 Hz at 50 Hz fundamental) and above the 3rd (150 Hz). That's a common sweet spot for detuned reactors in industrial networks — it avoids amplifying the 5th while still providing enough impedance to protect the capacitor bank from harmonic overload.

Mounting and environment — IP00, thermal class H

The thermal class H (IEC 60085) allows a 180 °C hot-spot temperature, so it can live in a warm cabinet without derating, provided the ambient stays at or below 40 °C. Dimensions are 0.3 m wide by 0.269 m tall by 0.211 m deep — account for that footprint plus clearance around the ventilation paths when laying out the panel.

Frequently asked questions

What are the key electrical ratings for 4EU3032-0FE08-4BA0?

Rated voltage 525 V AC, rated current 59.1 A (max 65.7 A), 50 Hz, 3-phase, 0.0025 H inductance, 12.5% throttling factor, 50 kvar reactive power, resonant frequency 141 Hz.

What is the physical size of 4EU3032-0FE08-4BA0?

Width 0.3 m, height 0.269 m, depth 0.211 m. IP00 enclosure — install inside a cabinet.

MPN
4EU3032-0FE08-4BA0