Siemens 4EU3032-6MA08-0AA0

Siemens SIDAC 4EU3032-6MA08-0AA0 Filter Reactor, 95A, 400V,

MPN 4EU3032-6MA08-0AA0

Siemens SIDAC series, filter reactor, order code 4EU3032-6MA08-0AA0, 3-phase, 95 A rated / 105 A max, 400 V AC, 60 kvar, 0.51 mH, 5.67 % throttling, IP00.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

4EU3032-6MA08-0AA0 specifications
ParameterValue
IP ratingIP00
Depth0.211 m
Width0.3 m
Height0.269 m

Product details

The Siemens SIDAC 4EU3032-6MA08-0AA0 is a 3-phase filter reactor rated 95 A continuous with a 105 A maximum, designed for 400 V AC, 50 Hz line applications. The 0.00051 H inductance at 5.67 % relative throttling factor limits harmonic distortion and reduces dv/dt stress on downstream drive components. The 60 kvar reactive power rating indicates reactive compensation capacity at rated voltage. The IP00 enclosure is an open-frame component for panel installation.

What the thermal class and resonant frequency tell a field engineer

Thermal class H per IEC 60085 means the insulation system can handle a 180 °C hot-spot temperature — this reactor can sit in a warm cabinet (40 °C ambient rated) and still carry full current without derating. The resonant frequency of 210 Hz is the point where the reactor's inductance and the system's capacitance form a parallel resonance; a field engineer checking for harmonic excitation should verify the dominant harmonics (5th at 250 Hz, 7th at 350 Hz) don't align with that 210 Hz notch.

Termination and mounting — what you're wiring into

Main circuit connections use flat connector / screw-type terminals — expect a bus-bar or ring-lug interface, not a spring-cage or pluggable connector. The footprint is 0.3 m wide by 0.269 m tall by 0.211 m deep, so plan for a panel cutout or mounting plate that accommodates those dimensions plus clearance for the terminals and airflow. IP00 means no built-in finger protection; the reactor must be mounted inside a locked or tool-accessible enclosure.

MPN