Skip to main content
Siemens 4EU3032-6MC08-1BA0 — Line/Load Reactors

Siemens 4EU3032-6MC08-1BA0 Filter Reactor, 50 kVAR, 440 V, I

MPN4EU3032-6MC08-1BA0

Siemens 4EU3032-6MC08-1BA0, 3-phase filter reactor, 50 kVAR, 440 V, 50 Hz, IP00, screw/flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Product details

3-Phase Filter Reactor for Harmonic Mitigation

The Siemens 4EU3032-6MC08-1BA0 is a 3-phase filter reactor rated at 50 kVAR reactive power at 440 V, 50 Hz. It is designed to suppress harmonic currents and limit voltage distortion in power distribution systems, typically installed ahead of variable-frequency drives or other non-linear loads. The reactor carries a 14 % impedance (P(%):14) and a resonant frequency of 135 Hz, which places its attenuation band in the 5th and 7th harmonic range — the dominant orders from six-pulse rectifiers.

The 50 kVAR rating at 440 V defines the reactive power compensation capacity. For a 400 V system, the effective kVAR derates proportionally with the square of the voltage ratio — expect roughly 41 kVAR at 400 V. The 14 % impedance (short-circuit voltage) means the reactor drops about 14 % of nominal voltage at rated current, which is typical for input line reactors used to limit inrush and harmonic injection. The 106 % ripple voltage figure at the listed conditions (0.5 / 6 / 5) indicates the reactor's ability to withstand voltage harmonics without saturating — relevant for drives with high switching frequencies. Terminals are screw/flat-type, suited for lug or bus-bar connections common in power distribution. The 40 °C ambient rating (TA/ISOKL:40 /H) defines the maximum surrounding air temperature for full-load operation; above that, derating applies per the thermal curve in the datasheet.

Sourcing is straightforward through independent distribution channels. For volume or scheduled deliveries, lead times are typically aligned with standard Siemens reactor production cycles — no last-time-buy urgency.

Integration Notes

Mount the reactor close to the drive line input to minimize cable inductance between the reactor and the drive. Screw/flat terminals accept ring lugs or bus bars; torque to the manufacturer's specification for the conductor size. The open-frame design requires at least 100 mm clearance around the core for natural convection cooling — forced airflow is recommended if mounted in a sealed cabinet above 40 °C ambient.

Frequently asked questions

What compliance documentation comes with this filter reactor?

The reactor is UL/CSA recognized under EN 61558-2-20. Standard documentation includes the declaration of conformity for CE marking; RoHS and REACH compliance declarations are typically available on request from the manufacturer or distributor.

Where can I buy 4EU3032-6MC08-1BA0 and how is it quoted?

This part is sourced through independent industrial distribution. It is quoted to order against an RFQ — submit your target quantity and delivery window for a firm price and availability confirmation. No minimum order quantity restrictions apply.

What is the closest alternative to 4EU3032-6MC08-1BA0 in this family?

Within the same Siemens reactor family, the closest parametric match would be a unit with identical kVAR, voltage, and impedance ratings but possibly different terminal configuration or enclosure rating. No direct pin-compatible drop-in exists without verifying the mounting footprint and terminal layout against the specific panel design.

MPN
4EU3032-6MC08-1BA0