Skip to main content
Siemens 4EU3052-0AM30-1BA0 — Line/Load Reactors

Siemens SIDAC 4EU3052-0AM30-1BA0 Output Reactor, 130A, 6000H

MPN4EU3052-0AM30-1BA0

Siemens SIDAC 4EU3052-0AM30-1BA0 output reactor, 3-phase AC, 130 A max, 6000 Hz rated, 0.3 mH, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3052-0AM30-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0003H
4EU3052-0AM30-1BA0 — Identification
ParameterValue
Product designationoutput reactor
4EU3052-0AM30-1BA0 — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EU3052-0AM30-1BA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU3052-0AM30-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3052-0AM30-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.26m
Width0.3m
Depth0.21m
4EU3052-0AM30-1BA0 — Other specifications
ParameterValue
Rated value6 000Hz

Product details

The Siemens SIDAC 4EU3052-0AM30-1BA0 is a three-phase output reactor (output choke) rated for 130 A maximum continuous current and 6000 Hz rated frequency, with an inductance of 0.3 mH. It sits between a variable-frequency drive and the motor to limit the rate of voltage rise (dV/dt) and reduce reflected-wave stress on motor windings, especially on long cable runs. Thermal class H (180 °C insulation system) per IEC 60085 gives it headroom for high-ambient or overload conditions up to 40 °C ambient temperature.

The 130 A maximum current (Ithmax) is the thermal continuous rating — size your drive output to stay at or below this value to avoid saturating the core. The 6000 Hz rated frequency (F1) is the fundamental output frequency the reactor is designed for; it will handle the switching harmonics from a PWM drive but is not a switching-frequency spec. The 0.3 mH inductance (300 µH) determines the dV/dt limiting effect — lower inductance gives less filtering, higher inductance increases voltage drop. The 3.9 % impedance (Uk) at rated conditions is a typical figure for this class of reactor. The flat-type terminals (flat connector) accept busbar or cable lugs; verify your lug width fits the terminal pad.

Deployment context

IP00 enclosure requires panel or cabinet mounting. Dimensions: 0.3 m width, 0.26 m height, 0.21 m depth.

Frequently asked questions

What are the physical dimensions of 4EU3052-0AM30-1BA0?

Width 0.3 m, height 0.26 m, depth 0.21 m. These are the external envelope dimensions; allow additional clearance for terminal access and airflow.

MPN
4EU3052-0AM30-1BA0