Skip to main content
Siemens 4EU3052-0EF00-1BA0 — Line/Load Reactors

SIDAC 4EU3052-0EF00-1BA0 Output Reactor, 250A 3-Phase AC Cho

MPN4EU3052-0EF00-1BA0

SIDAC output reactor, 4EU3052-0EF00-1BA0, 3-phase AC, 250A max, 8000Hz rated frequency, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3052-0EF00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00002H
4EU3052-0EF00-1BA0 — Identification
ParameterValue
Product designationoutput reactor
4EU3052-0EF00-1BA0 — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EU3052-0EF00-1BA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU3052-0EF00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3052-0EF00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.26m
Width0.3m
Depth0.21m
4EU3052-0EF00-1BA0 — Other specifications
ParameterValue
Rated value8 000Hz

Product details

The SIDAC 4EU3052-0EF00-1BA0 is a 3-phase AC output reactor rated for a maximum continuous current of 250A and a rated switching frequency of 8000Hz. This is the choke that sits between a variable-frequency drive output and the motor cable — it limits the rate of voltage rise (dV/dt) and reduces bearing currents on long cable runs. The 0.02 mH inductance and 8.36% impedance (UK) are sized for drives in the 225A continuous current class (I LN).

IP00 protection class means this reactor has no enclosure — it is intended for mounting inside a cabinet, not in a wet or dusty environment. Thermal class H insulation (rated for 180°C hot-spot) gives headroom in high-ambient panels, though the datasheet bases ratings at a 40°C ambient. Main circuit connections use flat-type terminals, so plan for busbar or compression lugs rather than ring terminals. Dimensions are 0.3m wide by 0.26m tall by 0.21m deep — account for that footprint plus clearance for airflow around the core.

Frequently asked questions

What is the switching frequency rating of this output reactor?

It is rated for a switching frequency of 8000Hz, with a minimum operating frequency of 500Hz. This covers the typical IGBT switching frequencies used in modern AC drives.

What is the maximum current rating?

The maximum continuous current is 250A. The continuous rated current (I LN) is 225A, which is the figure to use for thermal sizing in continuous-duty applications.

Where can I buy 4EU3052-0EF00-1BA0 and what is the price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — we confirm both at quote time.

What compliance documentation is available for this reactor?

The reactor is designed per EN 61558-2-20 (safety of transformers, reactors, and power supply units). Thermal class H is per IEC 60085. Specific RoHS/REACH/UL documentation should be requested at quote time as it may vary by production batch.

MPN
4EU3052-0EF00-1BA0