Skip to main content
Siemens 4EU3052-3UB00-0AA0 — Line/Load Reactors

Siemens 4EU3052-3UB00-0AA0 Mains Choke for Drive, 315 A, 480

MPN4EU3052-3UB00-0AA0

Siemens SIRIUS Netzdrossel f. FU, 4EU3052-3UB00-0AA0, 3-phase mains choke, 315 A max / 283.5 A rated, 480 V AC, 4 % voltage drop, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3052-3UB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000089H
Relative inductive voltage drop4%
4EU3052-3UB00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3052-3UB00-0AA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU3052-3UB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)216W
Power loss, iron core (W)129W
Rated ambient temperature40°C
4EU3052-3UB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3052-3UB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.221m

Product details

The Siemens 4EU3052-3UB00-0AA0 is a three-phase mains choke (line reactor) designed to sit between the supply and a variable-frequency drive. It limits harmonic current, reduces voltage notching, and protects the drive's DC-link capacitors from line transients. Rated for 315 A maximum continuous current and 283.5 A at the rated operating point, it handles the full-load draw of a substantial motor — think a 200+ kW induction machine on a pump or conveyor. Winding is thermal class H (180 °C) per IEC 60085, so it survives the heat inside a crowded panel without derating prematurely.

This is an open-frame choke — IP00, no enclosure. It mounts inside a cabinet, typically on a mounting plate or chassis, not on a DIN rail. The main circuit connects via flat-type terminals (bus-bar style), not ring lugs or screw clamps. Plan for a footprint of 0.3 m wide by 0.269 m tall by 0.221 m deep, and allow clearance around it for airflow: the coil dissipates 216 W and the iron core another 129 W, so forced ventilation or a generously sized cabinet is needed to keep ambient below the 40 °C rating point.

The choke carries UL and CSA recognition per EN 61558-2-20, which covers the safety of chokes and reactors for industrial use. That means it is accepted in North American panels without a separate field-evaluation sticker. The thermal class H winding and the 50/60 Hz rating are standard for global installation.

Frequently asked questions

What are the key electrical ratings of 4EU3052-3UB00-0AA0?

Three-phase AC, 400/480 V rated voltage, 50/60 Hz. Maximum continuous current 315 A, rated current 283.5 A. Inductance 89 µH, 4 % relative voltage drop at rated current. Coil power loss 216 W, iron-core loss 129 W.

Where can I buy 4EU3052-3UB00-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery needs.

MPN
4EU3052-3UB00-0AA0