Skip to main content
Siemens 4EU3052-4UB00-0AA0 — Line/Load Reactors

Siemens 4EU3052-4UB00-0AA0 Mains Choke, 450A, 28 µH, 3-Phase

MPN4EU3052-4UB00-0AA0

Siemens 4EU3052-4UB00-0AA0 mains choke (Netzdrossel f. FU), 3-phase, 450 A rated / 500 A max, 28 µH, 2% voltage drop, 400/480 V AC, 50/60 Hz, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3052-4UB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000028H
Relative inductive voltage drop2%
4EU3052-4UB00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3052-4UB00-0AA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU3052-4UB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)216W
Power loss, iron core (W)129W
Rated ambient temperature40°C
4EU3052-4UB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3052-4UB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.221m

Product details

Mains choke for variable-frequency drives

The Siemens 4EU3052-4UB00-0AA0 is a three-phase mains choke (line reactor) designed for the input side of variable-frequency drives. The 2% drop reduces harmonic distortion and limits inrush current without dropping so much voltage that the drive DC bus starves under load. The IP00 enclosure means it's an open-frame component — mount it inside a panel or cabinet that provides the physical and electrical protection. Connections are via flat-type terminals, sized for lug or bus-bar terminations typical of high-current power paths.

Power loss and thermal class

Total power loss splits into 216 W in the coil and 129 W in the iron core at rated load and 40 °C ambient. Thermal class H (IEC 60085) means the insulation system withstands 180 °C hot-spot temperature — headroom for sustained high current in a warm enclosure. The 40 °C ambient rating is the baseline; derate for higher ambient or forced-air cooling requirements.

Mature lifecycle status. UL and CSA recognized per EN 61558-2-20.

Frequently asked questions

What are the physical dimensions of 4EU3052-4UB00-0AA0?

Depth is 0.221 m, width is 0.3 m, and height is 0.269 m.

Does this choke have UL or CSA approval?

Yes, it is UL and CSA recognized per EN 61558-2-20.

MPN
4EU3052-4UB00-0AA0