Skip to main content
Siemens 4EU3052-8UB00-0AA0 — Line/Load Reactors

Siemens 4EU3052-8UB00-0AA0 Mains Choke, 309A, 500V, 3-Phase

MPN4EU3052-8UB00-0AA0

Siemens SENTRON 4EU3052-8UB00-0AA0 mains choke (Netzdrossel f. FU), 3-phase, 500V AC, 309A max / 278A rated, 0.08mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3052-8UB00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value500, 500V
Relative inductive drop in voltage on the measurement level current, voltage and frequency3%
Power loss [W] of the coil160W
Power loss [W] of the iron core105W
Operating frequency rated value50 ... 60Hz
Phase number3
Ambient temperature rated value40°C
Depth0.221m
Width0.3m
Height0.269m
Thermal class acc. to IEC 60085H
Rated value278A
Protection class IPIP00
Inductivity rated value0.00008H

Product details

The Siemens 4EU3052-8UB00-0AA0 is a three-phase mains choke (Netzdrossel f. FU) designed for the input side of a frequency converter. It operates at 500 V AC, 50/60 Hz, and carries a maximum current of 309 A with a rated current of 278 A. The 0.08 mH inductance and 3 % relative inductive voltage drop smooth line-side harmonics and limit inrush current — a standard role for a line reactor in a drive cabinet. Rated for an ambient temperature of 40 °C and built to thermal class H per IEC 60085, the choke dissipates 160 W in the coil and 105 W in the iron core under rated conditions. That thermal class means the insulation system can handle a 180 °C hot-spot temperature, which gives headroom in a crowded panel as long as airflow is adequate.

Mounting and connection

The choke measures 0.3 m wide, 0.269 m tall, and 0.221 m deep. Main circuit connections are flat-type terminals (bus-bar or large lug), sized for the 309 A path.

Frequently asked questions

What are the key ratings of 4EU3052-8UB00-0AA0?

It is a 3-phase mains choke rated for 500 V AC, 50/60 Hz, with a maximum current of 309 A and a rated current of 278 A. Inductance is 0.08 mH with a 3 % voltage drop. It dissipates 160 W in the coil and 105 W in the iron core at rated load.

Where can I buy 4EU3052-8UB00-0AA0?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability.

MPN