Skip to main content
Siemens 4EU3621-0AV00-0A — Line/Load Reactors

Siemens 4EU3621-0AV00-0A Commutating Choke, 389A, 400V, 0.14

MPN4EU3621-0AV00-0A

Siemens SENTRON 4EU3621-0AV00-0A commutating choke for converter, 3-phase, 400V AC, 389A rated current, 432A max, 0.14mH inductance, IP00, flat-type terminals, UL/CSA recognized.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3621-0AV00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.00014H
Relative inductive voltage drop8%

Identification

4EU3621-0AV00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU3621-0AV00-0A — Electrical
ParameterValue
Rated operating voltage400, 400V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz

Losses & Thermal

4EU3621-0AV00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)528W
Power loss, iron core (W)260W
Rated ambient temperature55°C

Approvals

4EU3621-0AV00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3621-0AV00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

The Siemens 4EU3621-0AV00-0A is a 3-phase commutating choke for converter applications, rated for 389 A continuous with a 432 A maximum at 60 Hz. It operates at 400 V AC, 50–60 Hz, and delivers 0.14 mH inductance with an 8% relative inductive voltage drop at rated current. That 8% drop is the key sizing figure — it limits the di/dt on the converter's semiconductors, so the choke must match the drive's switching frequency and current ripple requirements. The IP00 open-frame construction means it's intended for enclosure mounting, not standalone floor placement. Thermal class H (180 °C) insulation and a 55 °C ambient rating give it headroom in warm cabinets.

Mounting and Connections

Dimensions are 0.35 m wide × 0.321 m high × 0.237 m deep — a substantial block that needs a dedicated mounting plate or chassis rail, not a standard DIN rail. Main circuit connections are flat-type terminals, so plan for busbar or cable lugs with the correct hole pattern. The IP00 rating means it's open to dust and touch; the enclosure must provide the required ingress protection for the final installation.

Power Loss and Thermal Management

Total power loss at rated load is 788 W — 528 W in the coil and 260 W in the iron core. That's significant heat to vent; the enclosure must have forced-air cooling or sufficient natural convection clearance. The thermal class H winding (180 °C) provides a safety margin, but the 55 °C ambient limit means derating above that temperature is required.

Frequently asked questions

Where can I buy 4EU3621-0AV00-0A and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 4EU3621-0AV00-0A drop into a panel that was specified around 3RV6011-0CA10 without rewiring?

No — the 3RV6011-0CA10 is a motor-protective circuit breaker (S00 frame, 45 mm wide, DIN-rail mount), while this choke is a 350 mm wide, 237 mm deep open-frame component with flat-type terminals. The footprint, mounting method, and connection type are completely different; panel rework is required.

What compliance documentation does this brand provide for 4EU3621-0AV00-0A?

The part is UL/CSA recognized per EN 61558-2-20, which covers safety of transformers, reactors, and power supply units. Standard Siemens documentation includes a declaration of conformity and the UL recognition file number.