Siemens 4EU3621-0AV00-0A — Line/Load Reactors

Siemens 4EU3621-0AV00-0A Commutating Choke, 389A, 400V, 0.14

MPN4EU3621-0AV00-0A

Siemens SENTRON 4EU3621-0AV00-0A commutating choke for converter, 3-phase, 400V AC, 389A rated current, 432A max, 0.14mH inductance, IP00, flat-type terminals, UL/CSA recognized.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3621-0AV00-0A specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value400, 400V
Relative inductive drop in voltage on the measurement level current, voltage and frequency8%
Power loss [W] of the coil528W
Power loss [W] of the iron core260W
Operating frequency rated value50 ... 60Hz
Phase number3
Ambient temperature rated value55°C
Depth0.237m
Width0.35m
Height0.321m
Thermal class acc. to IEC 60085H
Rated value389A
Protection class IPIP00
Inductivity rated value0.00014H

Product details

The Siemens 4EU3621-0AV00-0A is a 3-phase commutating choke for converter applications, rated for 389 A continuous with a 432 A maximum at 60 Hz. It operates at 400 V AC, 50–60 Hz, and delivers 0.14 mH inductance with an 8% relative inductive voltage drop at rated current. That 8% drop is the key sizing figure — it limits the di/dt on the converter's semiconductors, so the choke must match the drive's switching frequency and current ripple requirements. The IP00 open-frame construction means it's intended for enclosure mounting, not standalone floor placement. Thermal class H (180 °C) insulation and a 55 °C ambient rating give it headroom in warm cabinets.

Dimensions are 0.35 m wide × 0.321 m high × 0.237 m deep — a substantial block that needs a dedicated mounting plate or chassis rail, not a standard DIN rail. Main circuit connections are flat-type terminals, so plan for busbar or cable lugs with the correct hole pattern. The IP00 rating means it's open to dust and touch; the enclosure must provide the required ingress protection for the final installation.

Total power loss at rated load is 788 W — 528 W in the coil and 260 W in the iron core. That's significant heat to vent; the enclosure must have forced-air cooling or sufficient natural convection clearance. The thermal class H winding (180 °C) provides a safety margin, but the 55 °C ambient limit means derating above that temperature is required.

Frequently asked questions

Where can I buy 4EU3621-0AV00-0A and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 4EU3621-0AV00-0A drop into a panel that was specified around 3RV6011-0CA10 without rewiring?

No — the 3RV6011-0CA10 is a motor-protective circuit breaker (S00 frame, 45 mm wide, DIN-rail mount), while this choke is a 350 mm wide, 237 mm deep open-frame component with flat-type terminals. The footprint, mounting method, and connection type are completely different; panel rework is required.

What compliance documentation does this brand provide for 4EU3621-0AV00-0A?

The part is UL/CSA recognized per EN 61558-2-20, which covers safety of transformers, reactors, and power supply units. Standard Siemens documentation includes a declaration of conformity and the UL recognition file number.