Skip to main content
Siemens 4EU3622-0EA00-1BA0 — Line/Load Reactors

Siemens 4EU3622-0EA00-1BA0 Commutating Choke, 450A Max, 750V

MPN4EU3622-0EA00-1BA0

Siemens SENTRON 4EU3622-0EA00-1BA0 commutating choke for converters, 3-phase, 750V AC, 450A maximum current, 405A rated current, 563A peak current, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3622-0EA00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000098H
Relative inductive voltage drop4%
4EU3622-0EA00-1BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3622-0EA00-1BA0 — Electrical
ParameterValue
Rated operating voltage750V
Number of phases3
Rated current (DC)551.4A
Voltage typeAC
Rated operating frequency50Hz
Peak current563A
4EU3622-0EA00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)293W
Power loss, iron core (W)170W
Rated ambient temperature40°C
4EU3622-0EA00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3622-0EA00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.227m

Product details

What this choke does in a converter circuit

The Siemens 4EU3622-0EA00-1BA0 is a 3-phase commutating choke for converters. Its 0.000098 H inductance at 405 A rated current and 750 V AC gives a 4 % relative inductive voltage drop at rated conditions.

Three current figures govern the fit. The 450 A maximum current is the thermal limit at 50 Hz. The 405 A rated current is the nominal operating current for the 4 % voltage drop. The 563 A peak current handles transient overloads.

Thermal management and enclosure requirements

Total power loss is 463 W — 293 W in the coil (copper losses) plus 170 W in the iron core (hysteresis and eddy-current losses). At 40 °C ambient, this heat must be removed from the enclosure. The thermal class H insulation (180 °C hot-spot) gives headroom, but the surrounding components and wiring must be rated for the radiated heat. Dimensions are 0.35 m wide × 0.321 m tall × 0.227 m deep — a substantial block that needs a dedicated mounting footprint and clearance for the flat-type terminals on the main circuit connections.

Frequently asked questions

What compliance documentation does this brand provide for 4EU3622-0EA00-1BA0?

The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC) for this order code. The design reference to EN 61558-2-20 in the description indicates it falls under the safety standard for chokes and reactors.

MPN
4EU3622-0EA00-1BA0