Siemens 4EU3622-3CA00-1BA0 — Line/Load Reactors

Siemens 4EU3622-3CA00-1BA0 Commutating Choke, 800 A AC, 400

MPN4EU3622-3CA00-1BA0
Active

Siemens 4EU3622-3CA00-1BA0 commutating choke for converter, 3-phase, 400 V AC, 800 A AC rated, 50 Hz, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU3622-3CA00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance2.6E-5H
Relative inductive voltage drop4%
4EU3622-3CA00-1BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3622-3CA00-1BA0 — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)720A
Number of phases3
Current (AC), max.800A
Rated current (DC)980.3A
Voltage typeAC
Rated operating frequency50Hz
Peak current1 000A
4EU3622-3CA00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)293W
Power loss, iron core (W)140W
Rated ambient temperature40°C
4EU3622-3CA00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3622-3CA00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.227m

Product details

The Siemens 4EU3622-3CA00-1BA0 is a 3-phase commutating choke (line reactor) for converter input circuits, rated 800 A at 400 V AC, 50 Hz. It limits current rise and reduces harmonic distortion on the line side of a variable-speed drive or rectifier. The 26 µH inductance and 4 % relative inductive voltage drop are sized for the converter's commutation notches — not a general-purpose line filter.

The 800 A continuous AC rating defines the maximum steady-state line current this choke can carry without exceeding a 40 °C ambient. The 1 000 A peak current handles short-duration converter inrush without saturating the core — critical for ride-through on a loaded DC bus. Total power loss is 433 W (293 W coil + 140 W iron core) at rated conditions. That heat must be rejected from the panel — IP00 means no enclosure, so forced air or a cabinet fan is expected. Class H insulation (per IEC 60085) allows a 180 °C hot-spot limit, giving thermal headroom in a crowded cabinet.

Where this choke goes in the panel

Mounts on the panel floor or a support rail — no DIN-rail clip, so plan for bolted flat-bar connections. The flat-type terminals accept busbar or cable lugs; dimensions 350 mm wide × 321 mm tall × 227 mm deep. That footprint occupies roughly the space of a 200 A contactor plus its overload block. Place it between the line-side fuses and the drive input to catch commutation spikes before they reach the mains.

Listed as Active in Siemens' current portfolio. No phase-out notice or last-time-buy date on record.

Frequently asked questions

What compliance documentation is available for this choke?

The Siemens spec references EN 61558-2-20 and notes UL/CSA recognition. RoHS and REACH declarations are typically included in the manufacturer's documentation package — request these with your RFQ.

MPN
4EU3622-3CA00-1BA0