Siemens 4EU3622-5CA00-0AA0 — Line/Load Reactors

Siemens 4EU3622-5CA00-0AA0 Commutating Choke, 500V 450A AC

MPN4EU3622-5CA00-0AA0

Siemens 4EU3622-5CA00-0AA0 commutating choke for converter, 3-phase, 500V AC rated voltage, 450A AC max current, 62µH inductance, IP00, thermal class H.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3622-5CA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance6.2E-5H
Relative inductive voltage drop4%

Identification

4EU3622-5CA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU3622-5CA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)405A
Number of phases3
Current (AC), max.450A
Rated current (DC)551.4A
Voltage typeAC
Rated operating frequency50Hz
Peak current563A

Losses & Thermal

4EU3622-5CA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)293W
Power loss, iron core (W)171W
Rated ambient temperature40°C

Approvals

4EU3622-5CA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3622-5CA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.227m

Product details

The Siemens 4EU3622-5CA00-0AA0 is a commutating choke for converter applications, designed for 3-phase AC systems. It carries a rated voltage of 500V and a maximum AC current of 450A at 50Hz, with an inductance of 62µH. The IP00 rating means it's an open-frame component intended for installation inside a panel or enclosure — not for washdown or outdoor duty. Thermal class H insulation (rated for 180°C continuous) gives it headroom in high-ambient converter cabinets where standard class B or F chokes would derate.

What the ratings mean for fit

The 450A AC maximum current (at 50Hz) sets the thermal limit for continuous operation in a converter line. The 405A AC operational current is the figure to size against your drive's continuous output — if your converter draws 400A RMS at full load, this choke sits right at the working point with margin. The 563A peak current rating covers short-duration transients during commutation, which is the actual stress event a commutating choke sees. The 4% relative inductive voltage drop at rated current tells you how much voltage the choke consumes at full load — 20V out of 500V — which your drive's DC-link design needs to account for.

Integration notes

Physical footprint: 0.35m wide × 0.321m tall × 0.227m deep. The main circuit connects via flat-type terminals — expect bus-bar or heavy cable lugs, not screw-clamp blocks. IP00 means no built-in touch protection; mount it inside a locked cabinet with proper clearance to grounded metalwork. The 293W coil loss plus 171W iron-core loss means about 464W total heat to vent at full load — factor that into your cabinet cooling calculation, especially if the converter and other heat sources share the same enclosure.

Frequently asked questions

Will 4EU3622-5CA00-0AA0 drop into a panel designed for 5SJ3140-7?

No — 5SJ3140-7 is a 1-pole miniature circuit breaker with a 70mm installation depth and IP20 rating. The 4EU3622-5CA00-0AA0 is a 3-phase commutating choke with a completely different footprint (0.35m × 0.321m × 0.227m) and IP00 open-frame construction. Rewiring and panel rework would be required.

What compliance documentation is available for 4EU3622-5CA00-0AA0?

The evidence does not list RoHS, REACH, UL, or IEC certificates for this specific order code. The product designation references EN 61558-2-20 (safety of transformers, reactors, and power supply units). For specific compliance documentation, include the requirement in your RFQ so we can verify with the supply channel.

MPN
4EU3622-5CA00-0AA0