Siemens 4EU3622-5DA00-0AA0 — Line/Load Reactors

Siemens 4EU3622-5DA00-0AA0 Commutating Choke, 280A, 750V, 3-

MPN4EU3622-5DA00-0AA0

Siemens 4EU3622-5DA00-0AA0 commutating choke for converter, 3-phase, 750V AC, 280A max, 252A rated, 350A peak, IP00, class H insulation, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3622-5DA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value750, 750V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Peak current350A
Power loss [W] of the coil320W
Power loss [W] of the iron core180W
Operating frequency rated value60 ... 50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.227m
Width0.35m
Height0.321m
Thermal class acc. to IEC 60085H
Rated value252A
At DC rated value343.1A
Protection class IPIP00
Inductivity rated value0.00016H

Product details

The Siemens 4EU3622-5DA00-0AA0 is a three-phase commutating choke for converter applications, rated for 750 V AC operating voltage with a maximum continuous current of 280 A at 50/60 Hz. Its rated inductance is 0.00016 H (0.16 mH) with a relative inductive voltage drop of 4% at rated current and frequency. The choke is designed to limit current rise and reduce harmonic distortion in the DC link of variable-speed drives and power converters — a key component for protecting downstream semiconductors and smoothing commutation notches.

The 280 A maximum current and 252 A rated current define the continuous thermal capacity at 40 °C ambient. The 350 A peak rating handles short-duration overloads typical during motor startup or fault clearing. The 4% voltage drop at rated current and frequency is the impedance that limits di/dt — critical for matching the choke to the converter's DC-link design. The IP00 protection class means it is open-frame; it must be installed inside a cabinet or enclosure that provides the required ingress protection. The thermal class H insulation allows a 180 °C hot-spot temperature, giving headroom in high-ambient or overload conditions.

Integration notes

The choke measures 0.35 m wide, 0.321 m high, and 0.227 m deep. The IP00 enclosure means it must be mounted inside a panel with adequate ventilation; the total power loss is 500 W (320 W coil + 180 W iron core), so forced air or a derated enclosure is recommended if ambient exceeds 40 °C. The 0.16 mH inductance at 280 A is a substantial component — verify mounting footprint and busbar clearance before committing the panel layout.

Frequently asked questions

What are the key electrical ratings for 4EU3622-5DA00-0AA0?

The choke is rated for 750 V AC, 3-phase, with a maximum continuous current of 280 A, a rated current of 252 A, and a peak current of 350 A. Inductance is 0.00016 H (0.16 mH) with a 4% voltage drop at rated conditions.

Where can I buy 4EU3622-5DA00-0AA0?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What are the physical dimensions of 4EU3622-5DA00-0AA0?

The choke measures 0.35 m wide, 0.321 m high, and 0.227 m deep. It uses flat-type terminals for the main circuit and is rated IP00, so it requires enclosure mounting.

What compliance documentation is available for 4EU3622-5DA00-0AA0?

The part is designed to EN 61558-2-20 and carries thermal class H per IEC 60085. Standard Siemens documentation includes a declaration of conformity; specific RoHS/REACH/UL status should be confirmed at quote time.

MPN
4EU3622-5DA00-0AA0