Skip to main content
Siemens 4EU3622-6AA00-0AA0 — Line/Load Reactors

Siemens 4EU3622-6AA00-0AA0 Commutating Choke, 360 A, 91 µH

MPN4EU3622-6AA00-0AA0

Siemens 4EU3622-6AA00-0AA0 commutating choke for converter, 3-phase, 500 V AC, 360 A rated current, 91 µH inductance, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3622-6AA00-0AA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value500V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Peak current625A
Power loss [W] of the coil280W
Power loss [W] of the iron core212W
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.227m
Width0.35m
Height0.321m
Thermal class acc. to IEC 60085H
Rated value360A
At DC rated value490.1A
Protection class IPIP00
Inductivity rated value0.000091H

Product details

The Siemens 4EU3622-6AA00-0AA0 is a three-phase commutating choke for converter applications, designed to limit current rise and reduce harmonic distortion in the DC link of a variable-speed drive or rectifier. It carries a rated current of 360 A at 500 V AC, 50 Hz, with a peak current capability of 625 A — meaning it can handle the repetitive switching surges typical of a 6-pulse or 12-pulse converter without saturating the core.

Rated inductance is 91 µH (0.000091 H) at the rated current and frequency. This value sets the commutation notch and limits the rate of rise of fault current — critical for protecting the converter's thyristors or IGBTs. The relative inductive voltage drop is 4 % at rated current, which is typical for line-side chokes and tells you the impedance at 50 Hz. The DC rated current is 490.1 A, higher than the AC rating because DC operation avoids the skin-effect losses in the winding. If your application is a DC-link choke in a regenerative drive or a battery-fed inverter, this is the figure that governs thermal sizing. Total power loss breaks down as 280 W in the coil and 212 W in the iron core, summing to 492 W at rated load. That heat must be dissipated into the surrounding air — the IP00 enclosure means no fan or filter, so the panel must provide forced ventilation or enough free-air volume to keep the ambient below 40 °C, the rated operating temperature. Thermal class H per IEC 60085 means the insulation system can withstand a continuous hot-spot temperature of 180 °C. That gives headroom for overloads and high ambient conditions, but the 40 °C ambient rating is the design point — derate above that.

The main circuit connects via flat-type terminals — expect busbar or large-cable lugs, not screw-clamp blocks. Dimensions are 0.35 m wide by 0.321 m tall by 0.227 m deep, so it occupies a substantial footprint in the panel. IP00 means no ingress protection; install it in a clean, dry cabinet away from conductive dust or dripping water.

Frequently asked questions

What are the key electrical ratings for 4EU3622-6AA00-0AA0?

Rated current 360 A AC, peak current 625 A, rated voltage 500 V AC, inductance 91 µH, DC rated current 490.1 A, relative inductive drop 4 %.

Where can I buy 4EU3622-6AA00-0AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the physical size of 4EU3622-6AA00-0AA0?

Width 0.35 m, height 0.321 m, depth 0.227 m.

What compliance documentation is available for 4EU3622-6AA00-0AA0?

The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC) for this order code. The product is designed per IEC 60085 (thermal class H) and EN 61558-2-20 (choke standard).

MPN
4EU3622-6AA00-0AA0