Skip to main content
Siemens 4EU3622-8BA00-0AA0 — Line/Load Reactors

Siemens 4EU3622-8BA00-0AA0 Commutating Choke, 355A, 750V AC

MPN4EU3622-8BA00-0AA0

Siemens 4EU3622-8BA00-0AA0 commutating choke for converter, 3-phase, 750V AC, 355A max / 319.5A rated, 0.16mH, IP00, flat-type terminals, thermal class H.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3622-8BA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00016H
Relative inductive voltage drop4%

Identification

4EU3622-8BA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU3622-8BA00-0AA0 — Electrical
ParameterValue
Rated operating voltage750, 750V
Number of phases3
Rated current (DC)435A
Voltage typeAC
Rated operating frequency60 ... 50Hz

Losses & Thermal

4EU3622-8BA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)300W
Power loss, iron core (W)210W
Rated ambient temperature40°C

Approvals

4EU3622-8BA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3622-8BA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.227m

Product details

Commutating choke for converter duty

The Siemens 4EU3622-8BA00-0AA0 is a 3-phase commutating choke (line reactor) designed for converter input or DC-link circuits, rated for 750V AC operating voltage and a maximum continuous current of 355A at 50/60 Hz. The rated inductance is 0.16 mH with a relative inductive voltage drop of 4% at rated current (319.5A). This choke limits current rise and harmonics on the converter line side, protecting the rectifier and smoothing the DC bus.

What the ratings mean for fit

The 355A maximum current (Ithmax) at 50 Hz sets the thermal limit for continuous operation; the 319.5A rated current (ILN) is the nominal design point where the 4% voltage drop is measured. At DC, the choke is rated for 435A — useful for DC-link applications where the current is smoother. The 0.16 mH inductance is sized for typical 50/60 Hz converter switching frequencies; higher switching frequencies would see less filtering effect. The 300W coil loss plus 210W iron core loss sum to 510W total dissipation at rated load — this must be vented from the enclosure. Thermal class H (180°C) insulation means the choke can run hot without degrading the winding, but the 40°C ambient rating is the design point; derate above that.

Installation and integration

IP00 protection means the choke has no enclosure — it is an open-frame component intended for mounting inside a panel or cabinet. Dimensions are 0.35m wide, 0.321m tall, and 0.227m deep. The main circuit connection uses flat-type terminals, which require a busbar or cable lug with a flat mating surface. The choke is heavy and should be bolted to a mounting plate; no DIN-rail clip is provided. Ensure adequate clearance around the core for airflow and heat dissipation.

Frequently asked questions

What are the key electrical ratings for the 4EU3622-8BA00-0AA0?

3-phase, 750V AC operating voltage, 355A maximum continuous current at 50 Hz, 319.5A rated current, 0.16 mH inductance, 4% voltage drop at rated current. DC rating is 435A.

Will the 4EU3622-8BA00-0AA0 fit in a panel designed for a 5SQ2270-2YA04 breaker?

No. The 5SQ2270-2YA04 is a DIN-rail mounted miniature circuit breaker (IP20, 55mm deep). The 4EU3622-8BA00-0AA0 is an open-frame choke (IP00, 227mm deep, 350mm wide) that bolts to a mounting plate — completely different form factor and function.

Where can I buy the 4EU3622-8BA00-0AA0?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
4EU3622-8BA00-0AA0